238 • Vacon apfiff09 marine
Tel. +358
6
10.2.3
FB Control Word
FB Control Word
Signal
Comment
b0
ON
0>1 will reset the Switch On Inhibit state and bring the
drive to Ready Run. Should be reset after fault, Coast
Stop (b1) and Emergency Stop (b2) .
b1
Coasting Stop
0=Coast stop Active
1=Coast stop NOT active
b2
Quick Stop
0=Quick stop Active
1=Quick stop NOT active
b3
Start
Normal start command
0=Stop the drive
1=Start the drive
b4
Ramp Output to Zero
0=Force speed ramp output to zero
1=Release speed ramp output
b5
Ramp Hold
0=Hold speed ramp output
1=Release speed ramp
b6
Ramp Input to Zero
0=Force speed ramp input to zero
1=Release speed ramp input
b7
Fault Reset
0=No Action
1=Reset active faults
b8
Inching 1
Run the drive with defined constant speed
0=No Action
1=Run with constant speed
b9
Inching 2
Run the drive with defined constant speed
0=No Action
1=Run with constant speed
b10
Fieldbus Control Enable
Activate Fieldbus control when P3.1 =3/Fieldbus
0=Fieldbus Control NOT active
1=Activate Fieldbus Control
b11
Watch Dog
data communication between Profibus master and the
drive. Used to generate FB Communication -Fault.
b12
b13
b14
b15
B00: FALSE = OFF 1, TRUE = ON 1
OFF 1: -
ON: Voltage connected to drive and/or DC link charged if drive has the control.
B01: FALSE = Coast stop (OFF 2), TRUE = ON 2
Coast Stop - tate
ON 2: No Coast Stop command
B02: FALSE = Quick Stop (OFF 3), TRUE = ON 3
Quick Stop: Drive will make stop function defined by Quick Stop function parameter.
ON 3: No Quick stop command.
B03: FALSE = Stop Request, TRUE = Start Request
Stop Request: Drive will make stop defined by stop function.
Start Request: Start Command to the drive.