P2.16.10 Number of tries after underload fault trip ID738
This parameter determines how many automatic fault resets can be made during the
trial time after underload trip.
0 = No automatic fault reset after Underload fault trip
>0 = Number of automatic fault resets after Underload fault trip
P2.16.11 Fault Simulation ID1569
without actually making e.g.
over current situation. In drive interface point of view behaviour is identical to actual fault
situation.
B00 = +1 = Simulates over current fault (F1)
B01 = +2 = Simulates over voltage fault (F2)
B02 = +4 = Simulates under voltage fault (F9)
B03 = +8 = Simulates output phase supervision fault (F11)
B04 = +16 = Simulates earth fault (F3)
B05 = +32 = Simulates system fault (F8)
This fault simulation cover wide range of different faults in drive, see fault description
for details.
B06 = +64 = Simulates encoder fault (F43)
B07 = +128 = Simulates over temperature warning (W14)
B08 = +256 = Simulates over temperature fault (F14)
Warning bit needs to be active that fault will come in simulation. If fault bit is left
active drive will go fault state at warning limit when drive temperature will rice to
warning level.
B09 = +512 = Reserved