P2.16.4 Number of tries after undervoltage fault trip ID720
This parameter determines how many automatic fault resets can be made during the
trial time after undervoltage trip.
0 = No automatic reset
>0 = Number of automatic fault resets after undervoltage fault.
P2.16.5 Number of tries after overvoltage trip ID721
This parameter determines how many automatic fault resets can be made during the
trial time after overvoltage trip.
0 = No automatic fault reset after overvoltage fault trip
>0 = Number of automatic fault resets after overvoltage fault trip.
P2.16.6 Number of tries after overcurrent trip ID722
(NOTE! IGBT temp faults also included)
This parameter determines how many automatic fault resets can be made during the
trial time after overcurrent trip.
0 = No automatic fault reset after overcurrent fault trip
>0 = Number of automatic fault resets after overcurrent trip, saturation
trip and IGBT temperature faults.
P2.16.7 Number of tries after reference trip ID723
This parameter determines how many automatic fault resets can be made during the
trial time after 4 mA reference fault.
0 = No automatic fault reset after reference fault trip
>0 = Number of automatic fault resets after the analogue current signal
>4mA)
P2.16.8 Number of tries after motor temperature fault trip ID726
This parameter determines how many automatic fault resets can be made during the
trial time after calculated motor temperature fault trip.
0 = No automatic fault reset after Motor temperature fault trip
>0 = Number of automatic fault resets after the motor temperature has
returned to its normal level
P2.16.9 Number of tries after external fault trip ID725
This parameter determines how many automatic fault resets can be made during the
trial time after external fault trip.
0 = No automatic fault reset after External fault trip
>0 = Number of automatic fault resets after External fault trip