7.14.3
ID-controlled DO
This function is used to control any Digital output by any status that can be presented as bit.
The input signal is selected with the ID number and bit number.
Example: Most of the faults and warnings are normally presented in the common digital output.
With the ID-controlled DO function, it is possible to select a specific fault to be connected to the
digital output.
Warning Word 1 ID1174
Fault
Comment
b0
Motor stalled
W15
b1
Motor over temperature
W16
b2
Motor under load
W17
b3
Input phase loss
W10
b4
Output phase loss
W11
b5
Safe disable
W30 (Not implemented)
b6
FieldBus communication fault in slot D
W53 (Not implemented)
b7
FieldBus communication fault in slot E
W67 (Not implemented)
b8
Drive over temperature
W14
b9
Analogue input < 4mA
W50
b10
Not used
b11
Emergency stop
W63 (Not implemented)
b12
Run disabled
W62 (Not implemented)
b13
Not used
b14
Mechanical Brake
W58
b15
Not used
P2.14.5.1 ID.Bit Free Digital output control 1 ID1216
P2.14.6.1 ID.Bit Free Digital output control 2 ID1386 2
Select the signal for controlling the DO. The parameter has to be set in format xxxx.yy
where xxxx is the ID number of a signal and yy is the bit number. For example, the value
for DO control is
1174.02
. 1174 is the ID number of Warning Word 1. So the digital output
is ON when bit number 02 of the warning word (ID no. 1174) i.e.
Motor underload
is high.
P2.14.5.2 Free Digital Output selector ID1574 1
P2.14.6.2 Free Digital Output selector ID1325 2
Select the output terminal to be controlled with the parameter ID.bit Free Digital output
control.