7.14 ID Functions
Listed here are the functions that use the parameter ID number to control and monitor the signal.
7.14.1
Value Control
The value control parameters are used to control an input signal parameter.
P2.14.1.1 Control Input Signal ID ID1580
With this parameter you can select what signal is used to control selected parameter.
P2.14.1.2 Control Off Limit ID1581
This parameter defines the limit when the selected parameter value is forced to Off
value.
P2.14.1.3 Control On Limit ID1582
This parameter defines the limit when the selected parameter value is forced to On
value.
P2.14.1.4 Control Off Value ID1583
This parameter defines the value that is used when the used input signal is below Off
limit.
P2.14.1.5 Control On Value ID1584
This parameter defines the value that is used when the used input signal is above On
limit.
P2.14.1.6 Control Output Signal ID ID1585
This parameter defines which parameter is forced to On and Off values when selected
input signal exceeds the set limits.
P2.14.1.7 Control Mode ID1586
This parameter defines how the value control output behaves.
0 = SR ABS
Absolute input value is used to make a step change in the output between On and Off
values.
Off
value
On
value
Control
Off
value
Control
On
Value
Off
value
On
value
Negative Positive