apfiff09 marine vacon • 213
24-
6
P2.13.21 Control Slot selector ID1440
This parameter defines which slot is used as the main control place when two fieldbus
boards have been installed in the drive. When values 6 or 7 are selected, the drive uses
the Fast fieldbus profile. When the Fast fieldbus profile is used, s or other
C type boards cannot be used.
0 = All slots
4 = Slot D
5 = Slot E
6 = Slot D, Fast fieldbus support
7 = Slot E, Fast fieldbus support
Restrictions when Fast fieldbus support is activated:
1. Set first the Slave Address and the PPO type before selecting the Fast fieldbus mode.
2. Fast fieldbus profile is not available for all fieldbus board, contact factory for more
detail.
3. Service data of profibus board cannot be used.
4. Fieldbus board parameters cannot be accessed.
5. Profibus option board will operate only in ByPass mode.
6. Standard F53 fault detection is not available. WD Pulse monitoring needs to be used
to monitor communication faults.
P2.13.22 State Machine
Application has possibility to select what kind of state machine is used.
1: Standard
This mode makes fieldbus control behave as in explained in used fieldbus board manual.
2: ProfiDrive
This mode uses ProfiDrive type state machine in application level. This mode is possible
to use on fieldbus boards that does not have state machine itself or has possibility to
bypass state machine functionality in option board.
See chapter 9: Status and Control Word in detail
P2.13.23 Fieldbus Custom Minimum ID898
P2.13.24 Fieldbus Custom Maximum ID899
With these parameters its possible to define fieldbus reference input values scaling.
default is 0...10000 (0...100%)