7.12.13
Encoder Fault function
Encoder supervision gives fault in case there are no pulses from encoder. Requirement is that
reference is above 1 Hz and torque can reach 100 % level. This torque level can be adjusted by Iq
Fault limit parameter. This limit may need adjustment when torque limit is below 100 %.
Alternative method to detect encoder fault is Speed Error detection.
P2.12.12.1 Encoder Fast Hz Limit ID1801
Frequency limit where detection is made using fast detection.
P2.12.12.2 Fast Time Limit ID1805
Delay to encoder fault when fault happens above Encoder Fast Hz Limit.
P2.12.12.3 Iq Fault Limit ID1800
This defined Iq current limit what must be exceeded before situation is determine to be
encoder fault is pulses are missing from encoder at the same time.