Fieldbus communication
P2.12.10.1 Response to fieldbus fault ID733
Set here the response for a fieldbus fault if the active control place is fieldbus. For more
information, see the respective Fieldbus Board Manual.
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to Stop Function
3 = Fault, stop mode after fault always by coasting
4 = Warning, Previous frequency. Forced fault after delay. Only for profibus
communication
P2.12.10.2 Fieldbus fault delay ID1850
This how long drive will stay in run state after the communication has been lost if fault
response is set to 4 / Warning, previous frequency. If time is set to zero drive will remain
running until communication is established and stop command is given.
P2.12.10.3 Fieldbus Watch Dog delay ID1354
Defines delay when fault is generated when watch dog pulse is missing from fieldbus.
Set the time to zero to disable watchdog monitoring.
7.12.12
External Fault function
P2.12.11.1 Response to external fault ID701
P2.12.11.2 Response to external fault ID747
Defines the response to a digital input signal informing about an external condition
where the drive needs to react to. The external warning/fault indication can be connected
to a digital output.
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to Stop Function
3 = Fault, stop mode after fault always by coasting