7.12.6
Over Load Protection
load protection.
Over Load in based on internal counter that in increased when input value is above 105 % level and
decreased when below 105 % level, increase and decrease is happening every 100 ms.
Tripping is made when over load counter value is over 10 000.
With parameters it can be defined what is increase (Over load maximum step) at maximum defined
input level (Over Load Maximum Input). These points defines slope for the function. e.g. if input value
is middle of 105 % and Over Load Maximum Input values counter is increase half of the Over Load
Maximum step.
2.12.5.7 Response to over load ID1838
0 = No response
1 = Warning
2 = Fault
2.12.5.8 Over Load Signal ID1837
0 = Not Used
1 = Output Current (FW: MotorCurrentPU_100ms)
2 = Motor Torque
3 = Motor Power
2.12.5.9 Over Load Maximum Input ID1839
Input value level where over load counter is increased with maximum step defined by
P2.12.5.10
2.12.5.10 Over Load Maximum Step ID1840
Step in the over load counter when input value is at maximum input level defined by
P2.12.5.9.