7.12.2
Temperature sensor protections
The temperature protection function is used to measure temperatures and issue warnings and/or
faults when the set limits are exceeded. The marine application supports two OPT-BH and OPT-B8
board simultaneously. One can be used for the motor winding and one for the motor bearings.
P2.12.2.1 Number of used inputs in board 1 ID739 Board1 Channels
Select used temperature sensor combination with this parameter. See also the Vacon I/O
boards manual.
0 = Not used (ID Write, value of maximum temperature can be written from fieldbus)
1 = Sensor 1 in use
2 = Sensor 1 & 2 in use
3 = Sensor 1 & 2 & 3 in use
4 = Sensor 2 & 3 in use
5 = Sensor 3 in use
Note: If the selected value is greater than the actual number of used sensor inputs, the
display will read 200ºC. If the input is short-circuited the displayed value is 30ºC.
P2.12.2.2 Board 1 Temperature responce ID740
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to Stop Function
3 = Fault, stop mode after fault always by coasting
P2.12.2.3 Board 1 warning limit ID741 Board1
Set here the limit at which the PT100 warning will be activated.
When individual warning and fault limits are activated this is first board first channel
(1A).
P2.12.2.5 Board 1 fault limit ID742 Board1
Set here the limit at which the PT100 fault (F56) will be activated.
When individual warning and fault limits are activated this is first board first channel
(1A).
P2.12.2.5 Number of used inputs in board 2 ID743 Board2 Channels
If you have two temperature sensor boards installed in your frequency converter you can
choose here the combination inputs in use in the second board. See also the Vacon I/O
boards manual.
0 = Not used (ID Write, value of maximum temperature can be written from fieldbus)
1 = Sensor 1 in use
2 = Sensor 1 & 2 in use
3 = Sensor 1 & 2 & 3 in use
4 = Sensor 2 & 3 in use
5 = Sensor 3 in use