5
5.2 Monitoring values description
V1.1 Output frequency [#,## Hz] ID1
Output frequency to motor, updated at 10 ms time level.
V1.2 Frequency reference [#,## Hz] ID 25
Frequency reference to motor control, after speed share function. updates at 1
ms time level.
V1.3 Motor speed [ # rpm] ID 2
Motor speed in rpm
V1.4 Motor current [A] ID 3
Open loop:
1 s linear filtering.
Closed Loop:
32 ms filtering
Drive Synch Operation Master drive
This value is the total current of the system divided by number of drives in the
system (SbLastID). SbLastId cannot be changed; it needs to be set according to
how many drives are linked with system bus.
Drive Synch Operation Follower drive
This value is the current of the drive own power unit.
Current scaling in different size of units
Note: ID45, usually in Process data OUT 3 is scaled to be with one decimal
always.
Voltage
Size
Scale
208 240 Vac
NX0001 NX0011
100 0,01A
208 240 Vac
NX0012 NX0420
10 0,1A
208 240 Vac
NX0530
1 1A
380 500 Vac
NX0003 NX0007
100 0,01A
380 500 Vac
NX0009 NX0300
10 0,1A
380 500 Vac
NX0385 NX2643
1 1A
525 690 Vac
NX0004 NX0013
100 0,01A
525 690 Vac
NX0018 NX0261
10 0,1A
525 690 Vac
NX0325 NX1500
1 1A