P2.7.2.5 Stop State Flux ID1401
The amount of flux in percentage of the motor nominal flux maintained in the motor after
the drive is stopped. The flux is maintained for the time set by parameter ID1402
Flux Off
Delay
. This parameter can only be used in closed loop motor control.
7.7.2.1
Reduced flux function
Reduced flux function is used to decrease the magnetization current below a certain frequency limit.
This function is used in systems where high starting torque is not needed. This function CAN NOT be
used in any situation where motor nominal torque from zero speed is required.
P2.7.2.6 Reduced Flux frequency
A frequency point where flux starts to reduce to a level defined by
Reduced Flux Level
toward the zero speed.
P2.7.2.7 Reduced Flux level
This parameter defines the flux level when the output frequency is zero. The flux is
reduced linearly from ID1614 to zero frequency.
Output frequency
Motor
Magnetizerion
Red.
Flux Hz
Red. Flux