P2.6.3.9 Motoring Torque limit scaling ID485
The motoring torque limit is equal to parameter
any of the inputs is selected the motoring torque limit is scaled
between zero and parameter Motorin Torque Limit.
0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = FB Limit Scaling ID46 Monitoring value
P2.6.3.10 Generating torque limit scaling ID1087
The generator torque limit is equal to parameter
the inputs is selected the generator torque limit is scaled
between zero and parameter generator torque limit.
0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = FB Limit Scaling ID46 Monitoring value
7.6.3.4
Open Loop settings only
P2.6.3.9.1 Torque limit control P-gain ID610
This parameter defines the gain of the torque limit controller. It is used in Open Loop
control mode only.
P2.6.3.9.2 Torque limit control I-gain ID611
This parameter determines the I-gain of the torque limit controller. It is used in Open
Loop control mode only.
7.6.3.5
Closed Loop settings only
P2.6.3.10.1 Speed Control output limit ID1382
Torque limit for the speed controller. It affects both the positive and negative direction
torques.
P2.6.3.10.2 Speed Control positive limit ID646
Positive torque limit for speed controller output.
P2.6.3.10.3 Speed Control negative limit ID645
Negative torque limit for speed controller output.