P2.6.2.12 Scaling of Generating power limit ID1088
The generator power limit is equal to parameter Generator Power Limit if value 'Not
Used' is selected. If any of the inputs is selected the generator power limit is scaled
between zero and parameter P2.6.2.2 Generator Power Lim.
0 = Parameter
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = FieldBus Scaling ID46 (Monitoring Value)
P2.6.2.13 Undervoltage power limit DC level ID1611
This parameter defines the DC voltage level when the special power limit function is
activated. When DC voltage goes below this level the power level defined by under
voltage power limit will be activated.
P2.6.2.14 Undervoltage power limit ID1612
Defines the power limit that is used when DC voltage is below parameter Undervoltage
power limit DC level (P2.6.2.13). The function is deactivated when this parameter value is
zero.
Power Limit
DC Level
UV Level
UV P Lim