User`s manual

apfiff09 marine vacon • 137
24-
6
P2.6.2.1 Power Limit ID1722
General power limit for both motoring and generator side. This value is the final limit for
all scaling functions. This value should not be used for scaling but for the maximum
safety limit because the ramp up rate function is ineffective when this parameter is
changed.
P2.6.2.2 Generator power limit ID1290
Generator side power limit. This limit value is used for all scaling functions and power
limit ramp rate functions.
P2.6.2.3 Motoring power limit ID1289
Motoring side power limit. This limit value is used for all scaling functions and power
limit ramp rate functions.
P2.6.2.4 Generator Power limit 1 ID1513
P2.6.2.5 Generator Power limit 2 ID1514
Generator side power limit values when limits are activated by digital inputs. When both
digital inputs are activated the power limit is forced to zero.
P2.6.2.6 Motoring Power limit 1 ID1503
P2.6.2.7 Motoring Power limit 2 ID1504
Motoring side power limit values when limits are activated by digital inputs. When both
digital inputs are activated the power limit is forced to zero.
P Motoring power limit 1
P Motoring power limit 2
SEL4
B0
B1
IN00
IN01
IN10
IN11
F Power limit zero
P Motoring power limit
DI Motoring power limit 1
DI Motoring power limit 2
Limit for ramping control
P2.6.2.8 Power limit increase rate ID1502
Defines the power limit increase rate. Decreasing power limit will be in effect
immediately.
Input Limit
Power Limit
80 %
20 %
Internal Limit
10 % / s
6 s