P2.5.6.3 Digital output 1 on-delay ID487
P2.5.6.4 Digital output 1 off-delay ID488
P2.5.7.3 Digital output 2 on-delay ID491
P2.5.7.4 Digital output 2 off-delay ID492
With these parameters you can set on- and off-delays to digital outputs.
Signal
DO
On
Delay
Off
Delay
Figure 7-11. Digital outputs 1 and 2, on- and off-delays
P2.5.6.5 Invert digital output 1 ID1587
P2.5.7.5 Invert digital output 2
Inverts delayed digital output operation.
Signal
DO
On
Delay
Off
Delay
P2.5.6.6 ID.Bit Free DO 1 ID1217
P2.5.7.6 ID.Bit Free DO 2 ID1385
Select the signal for controlling the DO. The parameter has to be set in format xxxx.yy
where xxxx is the ID number of a signal and yy is the bit number. For example, the value
for DO control is
1174.02
. 1174 is the ID number of Warning Word 1. So the digital output
is ON when bit number 02 of the warning word (ID no. 1174) i.e.
Motor underload
is high.