Reference limit supervision
Active reference goes beyond the set supervision low limit/high limit.
17 =
External brake control
External brake ON/OFF control with programmable delay
18 =
Control from I/O terminals
IO control place is active.
19 =
Drive temperature limit supervision.
Drive temperature goes beyond the set supervision limits (par. ID354)
20 =
Motor rotation direction is different from the requested one. This happens in situation
when an external force makes the motor to rotate into different direction or when a
command for direction change has been given and the drive is still ramping down to
change direction.
21 =
External brake control inverted
External brake ON/OFF control; Output active when brake control is OFF.
22 =
Thermistor fault or warning
The thermistor input of option board indicates overtemperature. Fault or warning
depending on the response parameter.
23 =
Analogue input supervision
Analogue input supervision function, Set Reset type output function.
24 =
Fieldbus digital input data 1
25 =
Fieldbus digital input data 2
26 =
Fieldbus digital input data 3
Warning indication that requires pressing of Reset button. Normally the drive will
remove warning indication when the fault situation has passed. This output requires
that reset button is pressed before signal goes low after there has been a warning
trigger.
Select the signal for controlling the DO. The parameter has to be set in format xxxx.yy
where xxxx is the ID number of a signal and yy is the bit number. For example, the
value for DO control is 1174.02. 1174 is the ID number of Warning Word 1. So the
digital output is ON when bit number 02 of the warning word (ID no. 1174) i.e. Motor
underload is high.