User`s manual
130 • Vacon apfiff09 marine
Tel. +358
6
7.5.3
Delayed Digital Output 1 & 2
P2.5.6.1 Digital output 1 signal selection ID486
P2.5.7.1 Digital output 2 signal selection ID489
Connect the delayed digital output signal to the digital output of your choice with this
parameter. For more information about the TTF programming method, see chapter 4.
P2.5.6.2 Digital output function ID312
P2.5.7.2 Digital output 2 function ID490
0 = Not used
1 =
The AC drive is ready to operate.
Common reasons when eady signals are missing:
o Run enable signal is low
o DC Voltage is too low
o DC Voltage is too high
2 =
The frequency converter is modulating.
3 = Fault
A fault trip has occurred
nvert
No active faults in the drive.
5 =
Drive temperature has exceeded normal operation conditions. Temperature limit may
vary depending on drive type and size.
6 =
External fault or warning depending on parameter response to external fault
7 =
Fault or warning depending on parameter Response to the 4mA reference fault
- occurs if analogue reference is 4 20 mA and signal is <4mA
8 =
Always if a warning is on
9 =
Drive output frequency is negative
peed
The jogging, preset or inching speed has been activated with digital input.
11 =
Induction motor: speed is within nominal slip of the reference.
PMS motor: output frequency is within 1 Hz of the reference.
12 =
One of the limit regulators is active.
13 =
Output frequency limit 1 supervision
The output frequency goes outside the set supervision low limit/high limit.
14 =
Output frequency limit 2 supervision
The output frequency goes outside the set supervision low limit/high limit.
15 =
Torque limit supervision
The motor torque goes beyond the set supervision low limit/high .