User`s manual

126 Vacon apfiff09 marine
Tel. +358
6
7.5.2
Analogue outputs 1 & 2 & 3 & 4
P2.5.2.1 Analogue output 1 signal selection ID464
P2.5.3.1 Analogue output 2 signal selection ID471
P2.5.4.1 Analogue output 3, signal selection ID478
P2.5.5.1 Analogue output 4, signal selection ID1527
Connect the AO1 signal to the analogue output of your choice with this parameter.
P2.5.2.2 Analogue output function ID307
P2.5.3.2 Analogue output 2 function ID472
P2.5.3.2 Analogue output 3, function ID479
P2.5.3.2 Analogue output 4, function ID1520
This parameter selects the desired function for the analogue output signal.
0 Not used
Analogue output is forced to 20 % (= 2 V/4 mA)
1 Drive Output Frequency
Output frequency from zero to maximum frequency.
2 -
Freq. reference from zero to maximum frequency
3 Motor speed
Motor speed from zero speed to motor synchronous speed
4 Drive Output Current
Drive output current from zero to motor nominal current
5 orque
Motor torque from zero to motor nominal torque (100 %)
6 Motor Power
Motor power from zero to motor nominal power (100 %)
7 Mot Voltage
Drive output voltage from zero to motor nominal voltage
8 DC-link volt
500 V unit: DC voltage from zero to 1000 Vdc
690 V unit: DC voltage from zero to 1317 Vdc
9 AI1
Unfiltered Analogue input 1 signal
10 AI2
Unfiltered Analogue input 2 signal
11 -max
Output frequency from minimum frequency to maximum frequency