User`s manual

apfiff09 marine vacon • 125
24-
6
7.5.1.2
Fieldbus digital inputs connection
P2.5.1.24 Fieldbus input data 1 ID455
P2.5.1.26 Fieldbus input data 2 ID456
P2.5.1.28 Fieldbus input data 3 ID457
P2.5.1.30 Fieldbus input data 4 ID169
P2.5.1.32 Fieldbus input data 5 ID170
The data from the Fieldbus main control word can be led to digital outputs.
See used fieldbus board manual for location of these bits.
P2.5.1.25 Fieldbus digital input 1 parameter ID891
P2.5.1.27 Fieldbus digital input 2 parameter ID892
P2.5.1.29 Fieldbus digital input 3 parameter ID893
P2.5.1.31 Fieldbus digital input 4 parameter ID894
P2.5.1.33 Fieldbus digital input 5 parameter ID895
With these parameters you can define the parameter to be controlled by using FB Digital
input.
Example:
All option board inputs are in use and you still want to give DI: DC Brake Command
(ID416). You also have a fieldbus board in the drive.
Set parameter ID891 (Fieldbus digital input 1) to 416.
Now you are able to control DC Braking command from the fieldbus by Profibus control
word (bit 11).
It is possible to control any parameter in the same way if values 0=FALSE and 1=TRUE
are significant for that parameter. For example, P2.6.5.3 Brake Chopper (ID504) can be
controlled on and off using this function (Brake Chopper; 0 = Not Used, 1 = On, Run).
P2.5.1.34 Safe disable active ID756
Select the digital output to show the status of the Safe Torque Off.