User`s manual

124 Vacon apfiff09 marine
Tel. +358
6
P2.5.1.16 Output frequency limit 1 supervision ID447
The output frequency goes outside the set supervision limits defined in Supervision Lim
parameter group. The function can be set to monitor either the high or the low limit.
Limit and functions are selected in G2.5.8 Supervision Limits.
P2.5.1.17 Output frequency limit 2 supervision ID448
The output frequency goes outside the set supervision limits 2 defined in Supervision Lim
parameter group. The function can be set to monitor either the high or the low limit.
Limit and functions are selected in G2.5.8 Supervision Limits.
P2.5.1.18 Reference limit supervision ID449
Active reference goes beyond the set supervision low limit/high limit defined in
Supervision Lim parameter group. The function can be set to monitor either the high or
the low limit Limit. The functions are selected in G2.5.8 Supervision Limits.
P2.5.1.19 Temperature limit supervision ID450
The drive temperature goes beyond the set supervision limits defined in Supervision Lim
parameter group. The function can be set to monitor either the high or the low limit.
Limit and functions are selected in G2.5.8 Supervision Limits.
P2.5.1.20 Torque limit supervision ID451
The motor torque goes beyond the set supervision limits defined in Supervision Lim
parameter group. The function can be set to monitor either the high or the low limit.
Limit and functions are selected in G2.5.8 Supervision Limits.
P2.5.1.21 Motor thermal protection ID452
Motor thermistor initiates an overtemperature signal which can be led to a digital output.
The response is selected with P2.12.5.6 ThermistorF.Resp.
P2.5.1.22 Analogue input supervision limit ID453
The selected analogue input signal goes beyond the set supervision limits defined in
G2.5.8 Supervision Lim parameter group. The function can be set to monitor either the
high or the low limit.
P2.5.1.23 Limit Control active ID454
One or more of the drive limit controllers is active.