12 • Vacon apfiff09 marine
Tel. +358
4
4.3 Defining unused inputs/outputs
All unused inputs and outputs must be given the board slot value 0 and the value 1 also for
the terminal number. The value 0.1 is also the default value for most of the functions.
However, if you want to use the values of a digital input signal for e.g. testing purposes
only, you can set the board slot value to 0 and the terminal number to any number between
contact' and values 2 to 10 to 'closed contact'.
In case of analogue inputs, giving the value 1 for the terminal number corresponds to 0%
signal level, value 2 corresponds to 20%, value 3 to 30% and so on. Giving value 10 for the
terminal number corresponds to 100% signal level.