P2.4.5.3 AI3 custom setting minimum ID144
P2.4.5.4 AI3 custom setting maximum ID145
P2.4.6.3 AI4 custom setting minimum ID155
P2.4.6.4 AI4 custom setting maximum ID156
Set the custom minimum and maximum input levels for the AI3 signal within -
AI3/AI4 Output
Analogue
Input
100 %
0 %
0 %
100 %
40 %
Custom
Min
80 %
Custom
Max
P2.4.5.5. AI3 signal inversion ID151
P2.4.6.5 AI4 signal inversion ID162
The signal inversion function is useful in a situation when e.g. the PLC is sending power
limit to the drive using fieldbus. If the PLC is unable to communicate with the drive the
power limit from fieldbus to the drive would be zero. Using an inverted signal logic zero
value from PLC would mean maximum power limit. When inversion is needed for the
process data signal fieldbus values need to be written to Analogue input monitoring
signals. See parameter P2.4.5.1 AI3 Signal selection for details.
0 = No inversion
1 = Signal inverted
AI3/AI4 Output
Analogue
Input
100 %
0 %
40 %
Custom
Min
80 %
Custom
Max