User`s manual
116 • Vacon apfiff09 marine
Tel. +358
6
7.4.3.1
Sleep function
The drive can be stopped by sleep function when the analogue input falls below a certain value for a
certain time and speed functions become active.
100 %
0 %
Time [s]
20 %
Sleep Limit
Run
Status
Analogue
input
P2.4.3.9 AI1 sleep limit ID385
P2.4.4.9 AI2 sleep limit ID396
The drive is stopped automatically if the AI signal level falls below the Sleep limit defined
with this parameter. In joystick function, when input is between zero and ± this
parameter the drive will go to sleep state.
P2.4.3.10 AI1 sleep delay ID386
P2.4.4.10 AI2 sleep delay ID397
This parameter defines the time the analogue input signal has to stay under the sleep
limit in order to stop the drive.
P2.4.3.11 AI1 joystick offset ID165
P2.4.4.11 AI2 joystick offset ID166
Defines the frequency zero point as follows:
With this parameter on display, place the potentiometer in the assumed zero point and
press
Enter
on keypad.
Note: This will not, however, change the reference scaling.
Press
Reset
button to change the parameter value back to 0,00%.
P2.4.3.12 AI1 filter time ID1228 filter time
P2.4.4.12 AI2 filter time ID1232 AI2 filter time