P2.4.3.3 Analogue input signal 1 signal range ID320
P2.4.4.3 Analogue input signal 2 signal range ID325
0 -20mA/10V
Signal input ranges: 0...10 V and 0...20 mA.
Input signal is used from 0% to 100%.
Reference [Hz]
Analogue Input
100 %
0 %
Min Freq
Max Freq
1 -20 mA
Signal input ranges: 4 20 mA and 2 10 V
Input signal is used from 20 % to 100 %
Reference [Hz]
Analogue Input
100 %
0 %
Min Freq
Max Freq
20 %
2 10 - + 10 V
Signal input range: -10 V - + 10 V.
Input signal is used from -100 % to +100 %.
+10 V
0 V
Max Freq
- Max Freq
Analogue Input
Reference
-10 V