7.4.2.1
Forced control place
Digital inputs can be used to bypass parameter P3.1 Control Place, for example, in an emergency
situation when PLC is not able to send command to the drive.
SEL
G
IN 0
IN 1
SEL
G
IN 0
IN 1
DI IO Control
C IO Control
SEL
G
IN 0
IN 1
DI KP Control
C
KP Control
DI FB Control
SEL
G
IN 0
IN 1
C
FB Control
P
Control Place
Final Control Place
PC PC Control
C PC COntrol
Figure 7-9. Control place selection priority order
P2.4.2.18 Control from I/O terminal ID409
Contact closed: Force control place to I/O terminal
P2.4.2.19 Control from keypad ID410
Contact closed: Force control place to keypad
P2.4.2.20 Control from Fieldbus ID411
Contact closed: Force control place to fieldbus
P2.4.2.21 Parameter Set 1/Set 2 selection ID496
With this parameter you can select between Parameter Set 1 and Set 2.
Remember to put same input for both parameter set. Parameter sets cannot be changed
while drive is in run state.
Digital input = FALSE:
- Set 1 is loaded as the active set
Digital input = TRUE:
- The active set is saved to set 1
When making two parameter sets from the keypad
1. Set all parameters as needed for SET1
2.
3. Set all parameters as needed for SET 1
4.
Active Set shown in Status Word B9
Note: The parameter values are stored only when selecting parameter P6.3.1 Parameter
sets Store Set 1 or Store Set 2 or from NCDrive: Drive > Parameter Sets.
NOTE: When the control place is forced to change the values of Start/Stop, Direction
and Reference valid in the respective control place are used. The value of parameter
ID125 (Keypad Control Place) does not change. When the input opens the control
place is selected according to keypad control parameter P3.1 Control Place