P2.4.2.1 Start signal 1 ID403
Signal selection 1 for the start/stop logic.
This is for Start Place A, selected with P2.4.2.39
Default programming A.1.Default Forward start.
P2.4.2.2 Start signal 2 ID404
Signal selection 2 for the start/stop logic.
This is for Start Place A, selected with P2.4.2.39
Default programming A.2. Default Reverse start.
P2.4.2.3 Run enable ID407
When run enable is removed from the drive coasting stop is made always.
Drive will also show warning indication when run is disabled.
Contact open: Start of motor disabled
Contact closed: Start of motor enabled
P2.4.2.4 Reverse ID412
This reverse command is active when Start signal 2 is not used for reverse command
Contact open: Direction forward
Contact closed: Direction reverse
P2.4.2.5 Preset speed 1 ID419
P2.4.2.6 Preset speed 2 ID419
P2.4.2.7 Preset speed 3 ID419
Digital input selections for activating preset speeds.
Speed
Digital Input
Preset speed 1
Digital Input
Preset speed 2
Digital Input
Preset speed 3
Basic speed
0
0
0
Preset Speed 1
1
0
0
Preset Speed 2
0
1
0
Preset Speed 3
1
1
0
Preset Speed 4
0
0
1
Preset Speed 5
1
0
1
Preset Speed 6
0
1
1
Preset Speed 7
1
1
1
Related parameters
- G2.2.7 Constant Ref
P2.4.2.8 Motor potentiometer DOWN ID417
Contact closed: Motor potentiometer reference DECREASES until the contact is
opened. See details in G2.2.11 Motor Pot.