24-
6
3 - Start Pulse Stop Pulse
3-wire connection (pulse control):
DIN1: closed contact = start pulse
DIN2: open contact = stop pulse, falling edge.
Start 1
Start 2
Freq. Out
Figure 7-8. Start pulse/ Stop pulse.
The selections including the text 'Rising edge required to start' shall be used to
exclude the possibility of an unintentional start when, for example, power is connected,
re-connected after a power failure, after a fault reset, after the drive is stopped by Run
Enable (Run Enable = False) or when the control place is changed. The Start/Stop
contact must be opened before the motor can be started.
4 - Start Motor potentiometer UP
DIN1: closed contact = start forward
DIN2: closed contact = Increases motor potentiometer reference, see Motor
potentiometer function for more details.
5 Forward start rising edge Reverse start rising edge
DIN1: closed contact = start forward (Rising edge required to start)
DIN2: closed contact = start reverse (Rising edge required to start)
6 - - Start command rising edge Direction command
DIN1: closed contact = start (Rising edge required to start)
open contact = stop
DIN2: closed contact = reverse
open contact = forward
7 - Start command rising edge Run Enable
DIN1: closed contact = start (Rising edge required to start)
open contact = stop
DIN2: closed contact = start enabled
open contact = start disabled and drive stopped if running
8 RPuls-RPuls Start rising edge Stop rising edge
DIN1: closed contact = Start (Rising edge required to start)
DIN2: closed contact = Stop (Rising edge required to stop)