User`s manual

104 Vacon apfiff09 marine
Tel. +358
6
7.4 Input signals
7.4.1
Basic Settings
P2.4.1.1 Start/Stop logic selection ID300
This parameter defines start stop logic when using I/O control. Some of these selections
do not include everse command. Reverse command can be activated by a separate
0 Forward Start Reverse Start
Start 1: closed contact = start forward
Start 2: closed contact = start reverse
Start 1
Start 2
Freq. Out
2
1
Figure 7-6. Start forward/Start reverse
The first selected direction has the highest priority.
When the DIN1 contact opens the direction of rotation starts the change.
1 - Start command Direction command
Start 1: closed contact = start open contact = stop
Start 2: closed contact = reverse open contact = forward
Start 1
Start 2
Freq. Out
Figure 7-7. Start, Stop, Reverse
2 Start command Run Enable
DIN1: closed contact = start open contact = stop
DIN2: closed contact = start enabled open contact = start disabled and drive stopped
if running