P2.3.12.3 Speed Reference Interpolator TC ID1184
Set here time on what interval speed reference is updated. This function ramps the
reference between updated values.
Function is used when PLC is updating reference e.g. 100 ms time level but drive own
ramp is set much shorter to have fast response. When reference (Green) is used without
interpolator also output frequency would behave same way causing torque and current
spikes every time reference changes. When interpolator time is set to 100 ms output
frequency behaves as blue line.
Reference
Time * 100 ms