User`s manual

apfiff09 marine vacon • 101
24-
6
P2.3.9 Inching ramp ID1257
This parameter defines acceleration and deceleration times when inching is active.
Inching function will start the drive to reference without additional start command
regardless of control place. Inching function requires enabling from digital input before
command is accepted. Inching is also disabled if there is a start command active on the
active control place.
Other parameters for inching:
- Parameter: Inching Reference 1
- Parameter: Inching Reference 2
- Digital input selection: Enable Inching
- Digital input selection: Inching 1
- Digital input selection: Inching 2
P2.3.10 Reduction of acceleration and deceleration times ID401
Acceleration and deceleration times can be reduced with the input signal.
Input signal level zero means ramp times set by parameters. Maximum level equals one
tenth of the value set by parameter.
Adjust
Input [%]
Ramp Time Factor
100 %
10 %
Figure 7-4. Reducing acceleration and deceleration times
7.3.1
Quick Stop
P2.3.11.1 Quick stop mode ID1276
Selects the mode of stopping the drive when quick stop is active.
It is recommended to use same stop function in follower drives.
It is recommended to use same ramp time in both drives
0 Coast stop.
1 Ramp stop.
P2.3.11.2 Quick Stop Ramp time ID1256