Specifications

In accordance with IEC 947-2
In accordance with IEC 947-2 at 415V
A.7
A
M-PACT
Dimensions in mm
Recommended Minimum Copper Size
Rating
(A)
400 to 2500
800 to 3200
4000
Type
Withdrawable
Fixed
Withdrawable
Fixed
Withdrawable
Fixed
Withdrawable
Fixed
Withdrawable
Fixed
Withdrawable
Fixed
Frame
Size
1
2
2
Poles
3
4
3
4
3
4
Height
(1)
440
430
440
430
440
430
440
430
440
430
440
430
Width
329
322
429
422
419
412
549
542
419
412
549
542
Depth
(2)
390
328
390
328
390
328
390
328
482
328
482
328
Rating (A)
400
630
800
1000
1250
1600
2000
2500
3200
4000
Copper / phase
2 x 50 x 5
2 x 50 x 5
2 x 50 x 5
2 x 60 x 5
2 x 100 x 5
2 x 100 x 5
3 x 100 x 5
4 x 100 x 5
4 x 100 x 10
4 x 100 x 10 + 1 x 100 x 5
(1) Height is from mounting surface to highest part of the ACB
(2) Depth is from the cubicle door to the back terminals
S
1
50
50
50
50
40
50
50
50
50
40
50
40
143
143
105
84
175
351
N
1
65
65
65
50
40
65
65
65
50
40
65
50
143
143
105
84
105
211
H
2
80
80
80
65
60
80
80
80
65
60
80
50
176
176
143
105
60
128
S
1
50
50
50
50
40
50
50
50
50
40
50
40
143
143
143
84
287
574
N
1
65
65
65
50
40
65
65
65
50
40
65
50
143
143
105
84
196
392
H
2
80
80
80
65
60
80
80
80
65
60
80
50
176
176
143
105
98
209
S
1
50
50
50
50
40
50
50
50
50
40
50
40
143
143
143
84
224
490
N
1
65
65
65
50
40
65
65
65
50
40
65
50
143
143
105
84
224
490
H
2
80
80
80
65
60
80
80
80
65
60
80
50
176
176
143
105
163
347
S
1
50
50
50
50
40
50
50
50
50
40
50
40
143
143
143
84
351
765
N
1
65
65
65
50
40
65
65
65
50
40
65
50
143
143
105
84
351
765
H
2
80
80
80
65
60
80
80
80
65
60
80
50
176
176
143
105
255
542
S
2
50
50
50
50
40
50
50
50
50
40
50
40
143
143
143
84
418
888
N
2
65
65
65
50
40
65
65
65
50
40
65
50
143
143
105
84
418
888
H
2
80
80
80
65
60
80
80
80
65
60
80
50
176
176
143
105
418
888
S
2
50
50
50
50
40
50
50
50
50
40
50
40
143
143
143
84
571
1224
N
2
65
65
65
50
40
65
65
65
50
40
65
50
143
143
105
84
571
1224
H
2
80
80
80
65
60
80
80
80
65
60
80
50
176
176
143
105
571
1224
1250
20000
10000
5000
690
1000
8000
3 & 4
100%
1600
20000
10000
5000
690
1000
8000
3 & 4
100%
2000
20000
10000
5000
690
1000
8000
3 & 4
100%
2500
20000
10000
5000
690
1000
8000
3 & 4
100%
3200
20000
10000
5000
690
1000
8000
3 & 4
100%
4000
20000
10000
5000
690
1000
8000
3 & 4
100%
Breaker
Range
S
N
H
Rating
(A)
400 to 1600
400 to 4000
800 to 4000
Type
Fixed or
Withdrawable
Fixed or
Withdrawable
Fixed or
Withdrawable
Icu
50kA
65kA
80kA
Ics
50kA
65kA
80kA
Icw
(1 sec.)
50kA
65kA
80kA
Rated Short-Circuit Capacity
Weights (kg)
Fixed pattern ACB
400 to 1600A
2000 & 2500A
800 to 3200A
4000A
Withdrawable ACB
400 to 1600A
2000 & 2500A
800 to 3200A
4000A
Cassette only
400 to 1600A
2000 & 2500A
800 to 3200A
4000A
Frame
1
1
2
2
Frame
1
1
2
2
Frame
1
1
2
2
3 Pole
36
43
53
53
3 Pole
63
72
90
111
3 Pole
27
29
37
58
4 Pole
44
54
68
68
4 Pole
77
90
117
144
4 Pole
33
36
49
76
3 Pole
39
43
53
53
3 Pole
68
72
90
111
3 Pole
29
29
37
58
4 Pole
49
54
68
68
4 Pole
84
90
117
144
4 Pole
36
36
49
76
3 Pole
-
-
53
53
3 Pole
-
-
90
111
3 Pole
-
-
37
58
4 Pole
-
-
68
68
4 Pole
-
-
117
144
4 Pole
-
-
49
76
S range N range H range
1250 1600 2000 2500 3200 4000