Specifications

Free Air
(1)
The M-PACT ACBs may operate at higher ambient
temperatures than 40°C in certain installation
conditions. In this case the current rating in
Amperes should be reduced as indicated below.
A.6
Technical overview
A
GE Power Controls
Design and specifications are subject to changes without notice.
Characteristic
Rated current (40°C)
Rated service voltage (50/60 Hz)
Rated insulation voltage (50/60 Hz)
Rated impulse withstand voltage
Rated ultimate short-circuit
breaking capacity
Rated service short-circuit
breaking capacity
Rated short time withstand current
1 second
3 seconds
Rated short-circuit making capacity
Power dissipation at In
(Fixed breaker)
Power dissipation at In (Withdrawable)
Symbol
In
Ue
Ui
Uimp
Icu
Ics
Icw
Icw
Icm
Units
A
V
V
V
kA (rms)
kA (rms)
kA (rms)
kA (rms)
kA (peak)
Watts
Watts
220V
415V
500V
600V
690V
220V
415V
500V
600V
690V
415V
500V
600V
690V
S
1
50
50
50
50
40
50
50
50
50
40
50
40
143
143
143
84
16
33
N
1
65
65
65
50
40
65
65
65
50
40
65
50
143
143
105
84
11
22
S
1
50
50
50
50
40
50
50
50
50
40
50
40
143
143
143
84
39
75
N
1
65
65
65
50
40
65
65
65
50
40
65
50
143
143
105
84
27
53
S
1
50
50
50
50
40
50
50
50
50
40
50
40
143
143
143
84
63
127
N
1
65
65
65
50
40
65
65
65
50
40
65
50
143
143
105
84
43
86
H
2
80
80
80
65
60
80
80
80
65
60
80
50
176
176
143
105
23
49
S
1
50
50
50
50
40
50
50
50
50
40
50
40
143
143
105
84
106
211
N
1
65
65
65
50
40
65
65
65
50
40
65
50
143
143
105
84
68
135
H
2
80
80
80
65
60
80
80
80
65
60
80
50
176
176
143
105
36
77
20000
10000
5000
690
1000
8000
3 & 4
100%
20000
10000
5000
690
1000
8000
3 & 4
100%
20000
10000
5000
690
1000
8000
3 & 4
100%
20000
10000
5000
690
1000
8000
3 & 4
100%
Endurance (number of operating cycles)
Mechanical (with maintenance)
Mechanical (without maintenance)
Electrical (at rated current)
Number of poles
Rating of 4th pole
ACB type
Frame size
Temperature Deratings
The figures specified apply to withdrawable ACB’s with flat face vertical copper
connections
(1) Protection degree IP00. For use in enclosures with interior temperatures of
40°C to 70°C the relevant IP values can be applied.
Ambient
temperature
50°C
60°C
65°C
70°C
800
800
800
800
800
1000
1000
1000
1000
1000
1250
1250
1250
1250
1250
1600
1600
1445
1364
1280
2000
2000
2000
2000
1970
2500
2450
2232
2092
1970
3200
3200
3200
3019
2831
4000
3727
3367
3175
2978
Characteristics
Current Rating (A)
Performance Data
400 630 800 1000
Selectivity
Down-stream
Up-stream
400
800
1000
1250
1600
2000
2500
3200
4000
400
-
Full
Full
Full
Full
Full
Full
Full
Full
800
-
-
-
Full
Full
Full
Full
Full
Full
1000
-
-
-
-
Full
Full
Full
Full
Full
1250
-
-
-
-
-
Full
Full
Full
Full
1600
-
-
-
-
-
-
Full
Full
Full
2000
-
-
-
-
-
-
-
Full
Full
2500
-
-
-
-
-
-
-
-
Full
3200
-
-
-
-
-
-
-
-
-
4000
-
-
-
-
-
-
-
-
-
The following table shows the conditions to satisfy
full selectivity between UP-STREAM and
DOWN-STREAM devices.
Up-stream: M-PACT
Down-stream: M-PACT
ST delay 50 ms minimum between up-stream and
down-stream ACB Multiplication coefficient between
LT-ratings 1,56
Up-stream: M-PACT
Down-stream: RECORD or SPECTRA*
ST delay 50 ms minimum on M-PACT
Multiplication coefficient between LT ratings
*Record and Spectra are GE Power Controls
Moulded Case Circuit Breakers.
Down-stream
Spectra
Record
All ratings
250A
250A500A
500A1250A
LT coefficient
2
2
2,5
3