Specifications
C.9
C
M-PACT
Type S - 4 pole - Frame size 1, In = 400A to 1600A (max)
Type S - 3 pole - Frame size 1, In = 400A to 1600A (max)
Connected 414
Ventilation
Minimum clearance
to cassette side.
382 to door
35 Test
50 Disconnected
275 Fully withdrawn
Fascia
centre
Fascia
centre
Centre line of
operating panel
Centre line of
operating panel
Copperwork must be supported within 200 mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
Captive plate behind copper terminal, tapped M10 x 1.5 6H.
Minimum insertion of screw 16mm. Maximum insertion of screw 34mm.
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Connected 414
Ventilation
Minimum clearance to
cassette side.
382 to door
35 Test
50 Disconnected
275 Fully withdrawn
Fascia
centre
Fascia
centre
Centre line of
operating panel
Centre line of
operating panel
Copperwork must be supported within 200 mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
Captive plate behind copper terminal, tapped M10 x 1.5 6H.
Minimum insertion of screw 16mm. Maximum insertion of screw 34mm.
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Rear Access Connection
Withdrawable Pattern