Specifications

the unit should it be outside its cassette. Installers will
also find it particularly valuable for top-tier mounted
circuit breakers. Note: Users who already possess a
‘Titan’ handling truck for the original M-PACT cir-
cuit breaker can now obtain a conversion kit.
Automatic Transfer Switches
(A.T.S.)
The ATS ensures the continuity of electric supply to
an installation with minimum interruption by making
an automatic transfer from the normal supply to emer-
gency source. The emergency source can be either a
transformer or generator supply and the M-PACT air
circuit breakers are governed automatically by the
transfer controller, which selects the available source.
Circuit breaker insertion interlock
By incorporating this optional security interlock
device into a system, it prevents the inadvertent
insertion of an incorrectly rated withdrawable circuit
breaker into a cassette.
Cassette interlock
Available for withdrawable circuit breakers only, this
sophisticated interlock system secures the circuit brea-
ker in the disconnected position by means of a Ronis or
Profalux key. When the key is removed, the safety shut-
ters are automatically locked in position, thus preven-
ting access to the contacts and also ensuring that the
racking mechanism is not operable. For lock and key
details refer to key interlock facility section (p. A.23)
Sealed
door panel
escutcheon
An optional IP54
complete front door
panel is available
should a higher
degree of protection
be necessary.
Circuit breaker handling truck
Specifically designed for use with the M-PACT range,
this dedicated handling truck is a useful accessory
when faced with the task of inserting or removing the
circuit breaker from its panel, or when transporting
A.26
Technical overview
A
GE Power Controls