User Manual

Digital Security Controls Ltd. 28 Private and Confidential
Installation Manual DATE : 09/30/97 DRAFT
Sounder / Relay
System Peripheral
Communications
6XX = Test / Misc.
Tests
GG = Group Number. This 2 digit number is applied when using split arming / disarming function.
CCC = 3 digit Zone Number or User ID for Opening or Closing. When system status is sent, the CCC
field is defaulted to “000”
P = Check Sum
Add all 15 digits. If less than 15, complement and send. If greater than 15, repeatedly
subtract 15 until it is less then complement and send. (all 0’s = A’s)
Zone Alarms and Restorals can be programmed to send different messages to the monitoring station. For example, if the
reporting code for zone 5 is programmed with “34”, the monitoring station will receive the following message;
“*BURG* - ENTRY/EXIT - 5“ where 5 is the number of the zone which has been activated.
Different messages to be sent to the monitoring station are:
EVENT CODES (as per ADEMCO)
Event code Message as seen on receiver
Medical Alarms
1AA Medical *EMERG* - PERSONAL EMERGENCY - #
1A1 Pendant Transmitter *EMERG* - PERSONAL EMERGENCY - #
1A2 Fail to Report In *EMERG* - FAIL TO CHECK IN- #
Fire Alarms
11A Fire Alarm *FIRE* - FIRE ALARM - #
111 Smoke *FIRE* - SMOKE DETECTOR - #
112 Combustion *FIRE* - COMBUSTION - #
113 Water Flow *FIRE* - WATER FLOW - #
114 Heat *FIRE* - HEAT SENSOR - #
115 Pull Station *FIRE* - PULL STATION - #
116 Duct *FIRE* - DUCT STATION - #
117 Flame *FIRE* - FLAME SENSOR - #
118 Near Alarm *FIRE* - NEAR ALARM - #
Panic Alarms
12A Panic *PANIC* - PANIC - #
121 Duress *PANIC* - DURESS - #
122 Silent *PANIC* - SILENT PANIC - #
123 Audible *PANIC* - AUDIBLE PANIC - #
Burglar Alarms
13A Burglary *BURG* - BURGLARY - #
131 Perimeter *BURG* - PERIMETER - #
132 Interior *BURG* - INTERIOR - #
133 24 Hour *BURG* - 24 HOUR - #
134 Entry / Exit *BURG* - ENTRY / EXIT - #
135 Day / Night *BURG* - DAY / NIGHT - #
136 Outdoor *BURG* - OUTDOOR - #
137 Tamper *BURG* - TAMPER - #
138 Near Alarm *BURG* - NEAR ALARM - #
General Alarms
14A General Alarm *ALARM* - GENERAL ALARM - #
143 Expansion module failure *ALARM* - EXP. MODULE FAIL - #
144 Sensor tamper *ALARM* - SENSOR TAMPER - #
145 Module Tamper *ALARM* -
24 Hour Non-Burglary
15A 24 Hour non-Burg *ALARM* - 24 HR. NON-BURG - #
151 Gas detected *ALARM* - GAS DETECTED - #
152 Refrigeration *ALARM* - REFRIGERATION - #
153 Loss of Heat *ALARM* - HEATING SYSTEM - #
154 Water Leakage *ALARM* - WATER LEAKAGE - #
155 Foil Break *ALARM* - FOIL BREAK - #
156 Day Trouble *ALARM* - DAY ZONE - #
157 Low bottled Gas level *ALARM* - LOW GAS LEVEL - #
158 High Temp *ALARM* - HIGH TEMPERATURE - #
159 Low Temp *ALARM* - LOW TEMPERATURE - #
161 Loss of Air Flow *ALARM* - AIR FLOW - #
Fire Supervisory
2AA 24 Hour non-Burg SUPER - FIRE SUPERVISORY - #
2A1 Low Water Pressure SUPER - LOW WATER PRESSURE - #
2A2 Low CO2 SUPER - LOW CO2