User Manual
Digital Security Controls Ltd. 25 Private and Confidential
Installation Manual DATE : 09/30/97 DRAFT
This reporting code is transmitted when the Auto Arming sequence is canceled. Cancellation of the
sequence can be achieved by entering an access code (if required), activating a keyswitch zone input,
or by pressing the ‘Disarm’ Key on a WLSKey during the 1 minute pre-alert.
Special Opening
If the system is opened (disarmed) using any of the following methods, this reporting code will be
transmitted. (Maintenance Code, Keyswitch Zone (WLSKey), or Downloading).
Battery Trouble & Restoral
If the standby battery is low or disconnected, this trouble will be reported.
These reporting codes are sent to the System Maintenance Call Direction Group.
AC Failure & Restoral
If the AC supply has failed or has been restored, these reporting codes will be sent. There is a
programmable delay (001-255 minutes) which applies to both the trouble and the restoral.
These reporting codes are sent to the System Maintenance Call Direction Group.
Remote Sounder Trouble & Restoral
If the WLS9000 does not receive a supervisiory signal for ten seconds, this trouble condition will be logged
and communicated.
These reporting codes are sent to the System Maintenance Call Direction Group.
Fire Trouble & Restoral
An open circuit on any Fire Zone or the 2 wire smoke circuit will cause this trouble to be reported.
These reporting codes are sent to the System Maintenance Call Direction Group.
TLM Restoral
The TLM Restoral code is sent when the telephone line is restored from the trouble condition.
These reporting codes are sent to the System Maintenance Call Direction Group.
Failure to Communicate (Phone Numbers 1 & 2)
When events fail to communicate to either telephone number, this reporting code will be transmitted the
next time a communication is successful. The information will be transmitted in the following order.
OLD EVENT(S)
FAILURE TO COMMUNICATE (PHONE #1)
NEW EVENT(S)
If multiple FTC’s occur this FTC reporting code will create blocks of old information.
The FTC reporting code does not follow any call direction “group”. It is sent to every group’s call
directions upon transmissions of failed event transmissions.
When event(s) fail to communicate to a telephone number, there will not be an attempt to communicate
again until another event is sent to that phone number.
Event Buffer is 75% Full Since Last Upload
Whenever the 128 event internal buffer has reached a level of 75% full since the last successful upload
from a downloading computer, this reporting code will be transmitted.
This reporting code is sent to the System Maintenance Call Direction Group.
DLS Lead In and Lead Out
The DLS Lead Out Reporting codes will be transmitted by the panel every time DLS has completed a
successful DLS call to the panel. The DLS Lead In reporting code is transmitted two ways: after the
panel has been successfully called by DLS, but before the panel calls DLS back via the Downloading
Telephone Number when Callback is enabled; or upon a User Initiated Call-up.
These reporting codes are sent to the System Maintenance Call Direction Group with the System
identifier.
Zone Fault & Restoral
This reporting code is sent whenever a zone has entered the Fault state via a loss of supervisory on a