User's Manual
Table Of Contents
- 3G4010
- 3G (HSPA) Wireless Alarm Communicator
- installation manual V4.0
- Table of Contents
- Features
- Technical Specifications
- Ratings
- Parts
- 1
- Metal Casing
- 2
- 3G Antenna
- 3
- Antenna Mounting Hardware
- 4
- Anchor Screw Holes (3mm)
- 5
- Antenna Connector
- 6
- SIM Card Holder
- 7
- Status LEDs (see page 5)
- 8
- CON5 Battery Setting Jumper
- 9
- PC-Link Connector
- 10
- Tamper Switch
- 11
- Terminal Blocks
- 12
- Battery Leads
- 13
- Cable Entry
- 14
- Earth Ground Wire
- 15
- 12V/1.2Ah Battery
- 16
- 3G (HSPA) Radio Module
- Description
- 1. Unscrew the four screws securing the front panel to the cabinet. Remove the front panel.
- 2. Fit the 3G antenna [2]. Ensure the 3G antenna mounting hardware is fastened securely [3].
- 3. Attach the 3G radio module with the 3G antenna connector. Ensure that the connector is secure.
- 4. Turn on the 3G4010 and check the signal strength. 4.1 Connect the battery to the RED and BLK battery leads. 4.2 Connect the DC power source to +/- 12V terminals.
- 5. Allow the unit to power up.
- 6. Power down the 3G4010 by removing the DC power source and battery leads.
- 1. Using the cabinet, mark the four screw locations. Drill the anchor screw holes.
- 2. Using anchor screws (not provided), mount the cabinet to the wall.
- 3. Run the cables through the cable entry [13] or through the cabinet knockouts.
- 4. Complete the connections on the terminal blocks [11].
- 5. Reattach the front cover [1] securely to the cabinet.
- Simulated Landline Mode
- Panel Transmission Monitoring (PTM)
- Wireless Communications Sequence
- Inputs
- Outputs
- Activating the Outputs
- Swinger Shutdown
- Hardware Default
- Low Power Radio Shutdown
- Figure 2 - Wiring Diagram
- Figure 3 - Telephone Connection
- Figure 4 - Power Supply and Supervision Wiring Diagram
- Figure 5 - Fire Alarm Control Unit and 3G Transmitter
- Figure 6 - DSC Subscribers’ Unit Fire and 3G Transmitter Mounted in the Same Room
- Figure 7 - DSC Subscribers’ Unit Fire and 3G Wireless Transmitter Mounted Remotely
- Figure 8 -Connection Details for Wireless Network Supervision Relay and Redundant Fire Alarm Transmission
- Figure 9 - Connection Details for GSM Supervision Relay, Phone Line Supervision and Redundant Fire Alarm Transmission
- Description
- Limited Warranty
3G4010 Wiring Diagrams
14
Figure 3 - Telephone Connection
RED (R)
GREEN (T)
GRAY (R)
BROWN (T)
RJ-31X
RING
TIP
CONTROL PANEL
Incoming
Phone line
Handset
RI
TI
T1
R1
TIP
RING
4
321
5
3G4010
TIP T1 R1
RING
Figure 4 - Power Supply and Supervision Wiring Diagram
(BLK/WHT) +13.8VDC
(BLK ) GND
Control
Panel
EOL
Resistor
See Note 3
DSC
RM-2
RELAY
NC
C
NO
ZONE
TERMINALS
(See Note 1)
- +
+12VDC
GND
CONTROL PANEL
Aux Power
+ -
DSC
Supervision
Relay
See Note 2
17
16
151412
18
13
11
1097 86
19
Z4
Z3Z2
COM
20
Z1
AUX
+
PGM
3
PGM
1
PGM
4
COM
3G4010
PGM
3
DC IN
+ -
DSC ADP1310-NAU
Power Adaptor
NOTES
1. Program the Zone/Point as “Supervisory” type
with keypad only annunciation when in Alarm. Do
NOT use a point that is normally used for
2-Wire Smoke detectors.
2. The power Supervision relay, RM-2 is only used
when the 3G4010 is not powered by the control
panel. When the Radio is powered by the control
panel the relay is not required since a loss of input
power will generate a signal to the CMC.
3. Output 4 on the 3G4010 must be set as “Active
High” (default).
4. When powering the 3G4010 Radio by an
Auxiliary Power supply that has its own backup
battery, insert CON5 jumper on the radio and
remove the 1.2AH battery that came with the radio.
The following wiring diagrams (Figures 5 to 8) are examples of ULC Listed Fire Monitoring Installation
connections.