User's Manual

Table Of Contents
3G4010 Wiring Diagrams
13
Figure 2 - Wiring Diagram
5
41
2
36789
10
11
14
15 16
17
LE
LI
O1 O2 O3 O4
+OC
13
12
AS
L1
L2
L3
L4
1K5
This Connection is necessary
T
I
P
T
I
P
R
I
N
G
R
I
N
G
3G4010
32
DC IN
AUX
231
COM
41
COMT1 R1TIP RING
4
PGM ZONE
+
-
RJ-45
BATTERY
Sealed Rechargeable
12V / 1.2Ah
Typical battery charge: 30-50 mA
Recommended Model: 12V/1.2Ah or
12V/7Ah (for order code 3G4010 only)
Battery not required
if CON5 is ON
9-14VDC/ *700mA (max)
Earth-ground
Ground wire
from building
electrical installation
Inputs to be connected
to dry contact outputs
from alarm control panel
with 5.6KΩ EOL resistors
}
GROUND
CONNECTION
Tighten nut to break paint &
make good connection to
the cabinet.
Nut
Nut
Bolt
Lock washer
Lock washer
Star washer
Cabinet
Alarm Control Panel with
Dialler Interface
(Supports Contact ID format)
Panel Aux Power
or External Power
Supply (13.8V
DC
required for normal,
long-term operation)
Telephone Line
Connection
Supervision
Relay
RM1-UL Installations
RM1C-ULC Installations
WARNING: Incorrect connections may result in PTC failure or improper operation. Inspect wiring and ensure connections are correct before turning on.
Connect relay contacts to
a zone input on the alarm
control panel for 3G4010
troubles supervision
(24hr-type zone)
Optional
use of PGM
output (See
Programming)
WARNING!
HIGH VOLTAGE. DISCONNECT AC
POWER & TELEPHONE LINES
PRIOR TO SERVICING
All circuits are classified for UL installations as Power Limited/Class II Power Limited except for the battery leads which are not Power Limited. Do not route any wiring
over circuit boards. Maintain at least 1” (25.4mm) separation. A minimum 1/4” (6.4mm) separation must be maintained at all points between Power Limited wiring
and all other Non-Power Limited wiring. Route wires as indicated in the diagram.
NOTE: For ULC Commercial Fire and Burglary Installation requirements please refer to Figures 5, 6, 7 & 8 and to the ULC Installation Guide P/N 29002157R009.
(Use No. 26 AWG wires for
the connection to PSTN)
*Refer to Jumper 3 section
for current rating
For ULC Fire Monitoring installations fire alarm signals shall be sent
simultaneously over POTS line (using the dialler) and over the wireless
network (using 3G4010). Connect alarm output from control panel (PGM)
to the input on the 3G4010 that is programmed as a Fire Alarm Input.
Examples of Control Units/Subscribers Units or Power Supplies compatible
models: DSC PC1864, PC1832, PC1616, PC5204, etc.