User's Manual
Table Of Contents
- 3G4010
- 3G (HSPA) Wireless Alarm Communicator
- installation manual V4.0
- Table of Contents
- Features
- Technical Specifications
- Ratings
- Parts
- 1
- Metal Casing
- 2
- 3G Antenna
- 3
- Antenna Mounting Hardware
- 4
- Anchor Screw Holes (3mm)
- 5
- Antenna Connector
- 6
- SIM Card Holder
- 7
- Status LEDs (see page 5)
- 8
- CON5 Battery Setting Jumper
- 9
- PC-Link Connector
- 10
- Tamper Switch
- 11
- Terminal Blocks
- 12
- Battery Leads
- 13
- Cable Entry
- 14
- Earth Ground Wire
- 15
- 12V/1.2Ah Battery
- 16
- 3G (HSPA) Radio Module
- Description
- 1. Unscrew the four screws securing the front panel to the cabinet. Remove the front panel.
- 2. Fit the 3G antenna [2]. Ensure the 3G antenna mounting hardware is fastened securely [3].
- 3. Attach the 3G radio module with the 3G antenna connector. Ensure that the connector is secure.
- 4. Turn on the 3G4010 and check the signal strength. 4.1 Connect the battery to the RED and BLK battery leads. 4.2 Connect the DC power source to +/- 12V terminals.
- 5. Allow the unit to power up.
- 6. Power down the 3G4010 by removing the DC power source and battery leads.
- 1. Using the cabinet, mark the four screw locations. Drill the anchor screw holes.
- 2. Using anchor screws (not provided), mount the cabinet to the wall.
- 3. Run the cables through the cable entry [13] or through the cabinet knockouts.
- 4. Complete the connections on the terminal blocks [11].
- 5. Reattach the front cover [1] securely to the cabinet.
- Simulated Landline Mode
- Panel Transmission Monitoring (PTM)
- Wireless Communications Sequence
- Inputs
- Outputs
- Activating the Outputs
- Swinger Shutdown
- Hardware Default
- Low Power Radio Shutdown
- Figure 2 - Wiring Diagram
- Figure 3 - Telephone Connection
- Figure 4 - Power Supply and Supervision Wiring Diagram
- Figure 5 - Fire Alarm Control Unit and 3G Transmitter
- Figure 6 - DSC Subscribers’ Unit Fire and 3G Transmitter Mounted in the Same Room
- Figure 7 - DSC Subscribers’ Unit Fire and 3G Wireless Transmitter Mounted Remotely
- Figure 8 -Connection Details for Wireless Network Supervision Relay and Redundant Fire Alarm Transmission
- Figure 9 - Connection Details for GSM Supervision Relay, Phone Line Supervision and Redundant Fire Alarm Transmission
- Description
- Limited Warranty
3G4010 Wiring Diagrams
13
Figure 2 - Wiring Diagram
5
41
2
36789
10
11
14
15 16
17
LE
LI
O1 O2 O3 O4
+OC
13
12
AS
L1
L2
L3
L4
1K5
This Connection is necessary
T
I
P
T
I
P
R
I
N
G
R
I
N
G
3G4010
32
DC IN
AUX
231
COM
41
COMT1 R1TIP RING
4
PGM ZONE
+
-
RJ-45
BATTERY
Sealed Rechargeable
12V / 1.2Ah
Typical battery charge: 30-50 mA
Recommended Model: 12V/1.2Ah or
12V/7Ah (for order code 3G4010 only)
Battery not required
if CON5 is ON
9-14VDC/ *700mA (max)
Earth-ground
Ground wire
from building
electrical installation
Inputs to be connected
to dry contact outputs
from alarm control panel
with 5.6KΩ EOL resistors
}
GROUND
CONNECTION
Tighten nut to break paint &
make good connection to
the cabinet.
Nut
Nut
Bolt
Lock washer
Lock washer
Star washer
Cabinet
Alarm Control Panel with
Dialler Interface
(Supports Contact ID format)
Panel Aux Power
or External Power
Supply (13.8V
DC
required for normal,
long-term operation)
Telephone Line
Connection
Supervision
Relay
RM1-UL Installations
RM1C-ULC Installations
WARNING: Incorrect connections may result in PTC failure or improper operation. Inspect wiring and ensure connections are correct before turning on.
Connect relay contacts to
a zone input on the alarm
control panel for 3G4010
troubles supervision
(24hr-type zone)
Optional
use of PGM
output (See
Programming)
WARNING!
HIGH VOLTAGE. DISCONNECT AC
POWER & TELEPHONE LINES
PRIOR TO SERVICING
All circuits are classified for UL installations as Power Limited/Class II Power Limited except for the battery leads which are not Power Limited. Do not route any wiring
over circuit boards. Maintain at least 1” (25.4mm) separation. A minimum 1/4” (6.4mm) separation must be maintained at all points between Power Limited wiring
and all other Non-Power Limited wiring. Route wires as indicated in the diagram.
NOTE: For ULC Commercial Fire and Burglary Installation requirements please refer to Figures 5, 6, 7 & 8 and to the ULC Installation Guide P/N 29002157R009.
(Use No. 26 AWG wires for
the connection to PSTN)
*Refer to Jumper 3 section
for current rating
For ULC Fire Monitoring installations fire alarm signals shall be sent
simultaneously over POTS line (using the dialler) and over the wireless
network (using 3G4010). Connect alarm output from control panel (PGM)
to the input on the 3G4010 that is programmed as a Fire Alarm Input.
Examples of Control Units/Subscribers Units or Power Supplies compatible
models: DSC PC1864, PC1832, PC1616, PC5204, etc.