3G4010 3G (HSPA) WIRELESS ALARM COMMUNICATOR INSTALLATION MANUAL V4.0 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully read.
TABLE OF CONTENTS Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Identification of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IMPORTANT The equipment is fixed, wall-mounted and shall be installed in the position specified in these instructions. The equipment enclosure must be fully assembled and closed, with all the necessary screws/tabs and secured to a wall before operation.
Introduction The 3G4010 is a wireless communicator that sends alarm system information to an Sur-Gard System I, II, III or IV receiver through a 3G (HSPA) or 2G (GPRS) wireless network. This wireless communicator can be used with UL/ULC Listed compatible control units, as indicated in the manufacturer's installation instructions. NOTE: The 3G4010 is designed to work with SIA and the Contact ID communication format as described in SIA DC-05 Standard.
Identification of Parts Figure 1 - Parts 5 1 4 2 3 16 6 4 CON5 UA673 LE D1 OP E N LE D2 BAT NO BAT LE D3 LE D4 C ON3 S E R IAL NU MB E R 9 8 B AT + B AT - BA T NO BA T 10 11 + - 14 tie wrap 13 12 15 4 3G4010 All circuits are classified for UL installations as Power Limited/Class II Power Limited except for the battery leads which are not power limited. Do not route any wiring over circuit boards. Maintain at least 1” (25.4mm) separation. A minimum 1/4” (6.
This equipment 3G4010 is fixed and shall be installed by Service Persons only (Service Person is defined as a person having the appropriate technical training and experience necessary to be aware of hazards to which that person may be exposed in performing a task, and of measures available to minimize the risks to that person or other persons). It shall be installed and used within an environment that provides the pollution degree max 2, over voltages category II, in non-hazardous, indoor locations only.
Installing the 3G4010 CONNECT 24 Enrolment Information Only authorized dealers can enrol a 3G4010 with CONNECT 24. Dealer application forms and additional information on the CONNECT 24 Voice Response Unit (VRU) can be found at the CONNECT 24 website www.connect24.com. Please contact CONNECT 24 at the number below for assistance: USA 1-888-251-7458 CANADA 1-888-955-5583 NOTE: Step 1 should be performed before turning on the 3G4010 unit.
must be added to the 3G4010 current when determining the total draw on the host panel or power supply. Jumper CON5 does not limit the electrical current available on this output. Tamper (12-13) - These terminals are connected in series to the Tamper switch [10]. They will close when the cabinet is properly closed, and will open when the front cover is removed. Z1-Z4 (15-16-17-18) Programmable Inputs - These terminals can be set up to trigger events. Refer to ‘Inputs’ for details.
Operating Principles Simulated Landline Mode The simulated landline provides the alarm control panel (with dialer interface) with a back up line in the event of PSTN line trouble. If the voltage on the landline terminals (TIP/RNG) drops below 2.8V for a period of between 10 seconds and 45 seconds - depending on the device connected to the T1/R1 terminals- the 3G4010 switches the connected telephone device to the wireless network.
NOTE: For UL/ULC installations, connections between alarm panel outputs and 3G4010 inputs must be run in protective mechanical conduits. To reduce interference with the antenna, it is recommended that the metal conduit is not connected to the knock-outs in the top of the cabinet. Outputs The 3G4010 has four programmable outputs to activate in response to the associated events. Refer to the 3G4010 Wiring Diagram (Figure 2) at the back of this manual.
NOTE: If the unit has previously received programming from Connect 24, a hardware default is required to initiate the download of the latest configuration from Connect 24. Failure to do so will result in the unit transmitting with the previously programmed configuration. NOTE: A Hardware default must be performed when the SIM card is being swapped. Low Power Radio Shutdown When the battery voltage reaches the low battery threshold of 10.
Both Green Lights OFF Yellow Light Status No Signal Strength • If the red light is also FLASHING, refer to the RED light chart • Verify SIM card is activated • Ensure the antenna cable is plugged securely into the radio connector • If the SIM is active, connect a battery to the unit and test various locations for good/excellent signal strength • Connect an antenna extension kit (GS-15ANT, GS-25ANT or GS-50ANT) What It Means: Wireless Communicator Status/Communication Indicator Yellow Light ON • When u
Six Flashes Receiver Not Available • Contact the monitoring station to verify that the 3G4010 programming is correct (port, IP address, DNIS) • Contact your central station to verify they are not experiencing any receiver issues Seven Flashes DC Supply Trouble • Ensure the power source connected to the 3G4010 is providing 13.
The Red light will flash to indicate various trouble conditions outlined previously. If multiple trouble conditions are present, the red light will flash according to the highest priority trouble. For example, if both a 3G4010 low battery trouble (one flash) and an insufficient signal strength trouble (four flashes) are present; the red light will flash one time. Once the 3G4010 low battery trouble condition is corrected, the red light will then begin flashing four times.
General Information Enrolling a 3G4010 • The 3G4010 can be enrolled by going through the GVRU voice prompt, and completing the activation of the SIM card, and the initialization of the 3G4010 • The 3G4010 can also be enrolled using the Connect 24 website (www.connect24.com) SIM card activation period • A SIM card can take up to 24 hours to be activated by the provider. However, it typically takes less than an hour for the SIM card to be activated Checking SIM status • Go to www.connect24.com and login.
GROUND CONNECTION RJ-45 Earth-ground Ground wire from building electrical installation LE R I N G WARNING! Optional use of PGM output (See Programming) Sealed Rechargeable 12V / 1.2Ah BATTERY Battery not required if CON5 is ON 13 WARNING: Incorrect connections may result in PTC failure or improper operation. Inspect wiring and ensure connections are correct before turning on.
3G4010 Wiring Diagrams Figure 3 - Telephone Connection CONTROL PANEL RJ-31X RING RI TIP TI 4 R1 T1 3 GRAY (R) TIP RING 2 BROWN (T) GREEN (T) RED (R) 1 Incoming Handset Phone line 5 3G4010 TIP RING T1 R1 Figure 4 - Power Supply and Supervision Wiring Diagram CONTROL PANEL ZONE TERMINALS (See Note 1) Aux Power + + +12VDC - 2. The power Supervision relay, RM-2 is only used GND - NOTES 1. Program the Zone/Point as “Supervisory” type with keypad only annunciation when in Alarm.
3G4010 Wiring Diagrams Figure 5 - Fire Alarm Control Unit and 3G Transmitter Wiring Diagram for Fire Alarm Control Unit (with dialler) and 3G (HSPA/2G (GPRS) Transmitter (Passive Communication System) Fire Alarm Control Unit AUX Power (12V/700mA) 3G Wireless Transmitter 3G (HSPA) or 2G (GPRS) 3G4010 TIP/RING T1/R1 TIP/RING PSTN Zone Input Zone Inputs Outputs Fire Trouble PGM4 Output RM1C ULC Relay 3G4010 cabinet AC Input NOTES: - Power for 3G4010 shall be provided from Fire Alarm Control Unit
3G4010 Wiring Diagrams Figure 7 - DSC Subscribers’ Unit Fire and 3G Wireless Transmitter Mounted Remotely Alternate Wiring Diagram for DSC Subscribers’ Unit Fire and wireless Transmitter Passive Communication System -Using Phone Line Supervision Relay Fire Alarm Control Unit DSC Subscribers’ Unit Fire Outputs Fire Supervisory Trouble Zone Inputs AUX Power 12V/700mA PSTN T1/R1 Zone Input TIP/RING PGM1 PGM4 PGM1 RM1C ULC Relay RM1C ULC Relay RM1C ULC Relay PC5003C PC4050CR cabinet AC Input 3G (HS
3G4010 Wiring Diagrams Figure 8 -Connection Details for Wireless Network Supervision Relay and Redundant Fire Alarm Transmission Connection Details for Wireless Network Supervision Relay & Redundant Fire Alarm Transmission 3G4010 LE LI O1 O2 O3 O4+OC L1 L2 L3 L4 AS 1 2 143 15416+ 6 71 82PGM93 104 11AUX COM 12 13 17 DC IN18 ZONE 3 4T1 5 R1 1 TIP 2 RING COM Wireless Network Supervision Relay 5.
3G4010 Wiring Diagrams Figure 9 - Connection Details for GSM Supervision Relay, Phone Line Supervision and Redundant Fire Alarm Transmission Connection Details for Wireless Network Supervision Relay, Phone Line Supervision Relay and Redundant Fire Alarm Transmission 3G4010 1 TIP RING T1 R1 COM 2 3 PGM 4 AUX COM 1 2 3 ZONE + - 4 DC IN Redundant Fire Alarm Initiation 5.6 KOhm Wireless Network Supervision Relay 5.
IMPORTANT READ CAREFULLY: DSC Software purchased with or without Products and Components is copyrighted and is purchased under the following license terms: • This End User License Agreement ("EULA") is a legal agreement 3. COPYRIGHT between You (the company, individual or entity who acquired the Software and any related Hardware) and Digital Security Controls, a division of Tyco Safety Products Canada Ltd.
MODIFICATION STATEMENT Digital Security Controls has not approved any changes or modifications to this device by the user. Any changes or modifications could void the user’s authority to operate the equipment. Digital Security Controls n’approuve aucune modification apportée à l’appareil par l’utilisateur, quelle qu’en soit la nature. Tout changement ou modification peuvent annuler le droit d’utilisation de l’appareil par l’utilisateur.
Limited Warranty Digital Security Controls warrants the original purchaser that for a period of twelve months from the date of purchase, the product shall be free of defects in materials and workmanship under normal use. During the warranty period, Digital Security Controls shall, at its option, repair or replace any defective product upon return of the product to its factory, at no charge for labour and materials.