Installation Manual

Table Of Contents
3G4000 Wiring Diagrams
13
Figure 3 - Telephone Connection
RED (R)
GREEN (T)
GRAY (R)
BROWN (T)
RJ-31X
RING
TIP
CONTROL PANEL
Incoming
Phone lineHandset
RI
TI
TI
RI
TIP
RING
3G4000
TIP RING T1 R1 Z1 PGM1 Z2 PGM2 DC IN
+
-
1 2 3 4 5 6 7 98 10
Figure 4 - Power Supply and Supervision Wiring Diagram
Control
Panel
EOL
Resistor
See Note 3
CONTROL PANEL
DSC
Supervision
Relay
See Note 2
DSC
RM-2
RELAY
NC
C
NO
+12VDC
GND
Aux Power
+ -
3G4000
(BLK/WHT) +13.8VDC
(BLK ) GND
DSC ADP1310-NAU
Power Adaptor
TIP RING T1 R1 Z1 PGM1 Z2 PGM2 DC IN
+
-
1 2 3 4 5 6 7 9
ZONE
TERMINALS
(See Note 1)
- +
8 10
NOTES
1. Program the Zone/Point as “Supervisory” type
with keypad only annunciation when in Alarm.
Do NOT use a point that is normally used for
2-Wire Smoke detectors.
2. The power Supervision relay, RM-2 is only used
when the 3G4000 is not powered by the control
panel. When the Radio is powered by the control
panel the relay is not required since a loss of
input power will generate a signal to the CMC.
3. Output 4 on the 3G4000 must be set as “Active
High” (default).
4. When powering the 3G4000 Radio by an Auxiliary
Power supply that has its own backup battery,
insert JP3 jumper on the radio and remove the
1.2AH battery that came with the radio.
The following wiring diagrams (Figures 5 to 7) are examples of ULC Listed Fire Monitoring Installation
connections.