GS2055 HSPA/2G WIRELESS ALARM COMMUNICATOR TL255GS N G _N A_ U L_ U LC _F C C _I C _d ft_ 03 ETHERNET/INTERNET ALARM COMMUNICATOR X_ IM _E NOTE: This manual covers the following models for the North America: 05 5_ V .2 .5 GS2055-NA G S_ G S2 TL255GS-NA _T L2 55 GS2055-SM-NA 29 00 82 18 R 00 1_ N O VA TL255GS-SM-NA Installation Manual v2.
G Alarm Communicator Installlation Manual TABLE OF CONTENTS Warning: Installer Please Read Carefully . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Communicator Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2G Alarm Communicator Installlation Manual Warning: Installer Please Read Carefully WARNING: INSTALLER PLEASE READ CAREFULLY Note to Installers Motion Detectors The Warnings on this page contain vital information. As the only individual in contact with system users, it is the installer’s responsibility to bring each item in this Warning to the attention of all users of this system.
Keypad Data Display 2G Alarm Communicator Installlation Manual GENERAL INFORMATION Domain Name Service (DNS) programming is not permitted in UL/ULC listed systems. KEYPAD DATA DISPLAY • Section-Toggle Options: The number is displayed when Toggle is ON, the number is not displayed when Toggle is OFF. (e.g., Toggle Options displays: “[--3--6--]”. Options 3 and 6 are ON, all others are OFF). Pressing keys 1 through 8 will alternately turn the Toggle ON and OFF.
2G Alarm Communicator Installlation Manual General Information COMMUNICATOR TECHNICAL SPECIFICATIONS GENERAL INFORMATION _I C _d ft_ 03 All versions of the HSPA/2G and Ethernet Alarm Communicator, operate on a HSPA/2G network and are housed inside the Self Contained Wireless (SCW) 9055/9057. The Communicators use an Internal Antenna only.
Ratings 2G Alarm Communicator Installlation Manual RATINGS Table 4: Communictor Electrical Ratings GS2055 Cellular Only Model Power Supply Ratings Input Voltage Current Consumption Standby Current (@ 3.7V) Alarm (Transmitting) Current) Antenna Specifications Dual band Antenna Environmental Specifications Operating Temperature Humidity Mechanical Specifications Board Dimensions (mm) Weight (grams) TL255GS Ethernet and Cellular 3.5 / 3.9 / 4.
2G Alarm Communicator Installlation Manual Encryption NOTE: Following initial installation, you can log in to the Connect24 website at any time to re-configure the Communicator remotely, using the account created for this installation. For more information, refer to the Connect24 website. Before leaving the installation site, the Communicator GS2055 or TL255GS shall be connected via an APPROVED (acceptable to the local authorities) Network Interface Device (NID) (e.g.
Inserting/Removing the SIM Card 2G Alarm Communicator Installlation Manual INSERTING/REMOVING THE SIM CARD Figure 3: SIM Card Pinouts 1.Remove the front cover of the SCW Control Panel to access SIM card holder. DG0009396 2.Remove power from the SCW and disconnect the backup battery SIM Card Pinouts connections. 3.On the SIM card holder push gently to slide the cover towards OPEN as indicated by the arrow on SIM holder.
2G Alarm Communicator Installlation Manual SMS Command and Control Functions 7. Panel Section [401]: Toggle Option [1] must be set to ON in order to perform panel DLS session through Cellular or Ethernet data channel. NOTE: Keep a record of the SIM card telephone number, it is required by users for SMS Command and Control functions.
System Options 2G Alarm Communicator Installlation Manual ETHERNET/CELLULAR PROGRAMMING OPTIONS The Programming Sections described in this document can be viewed at the SCW LCD. To start programming enter: [*][8][installer code] [851][# # # ], Where # # # is the 3 digit Section number referenced in this section. The Programming Worksheets at the end of this document can be used to record the new values when programming changes have been made from the default values.
2G Alarm Communicator Installlation Manual System Options NOTE: Commercial supervision is more data intensive than residential supervision and should only be used when required to meet the approval for the installation. [4] Primary Path Default (OFF - TL255GS) (ON - GS2055) ON: Cellular channel is the primary path. Ethernet channel is the secondary path, if it exists. OFF: Ethernet channel is the primary path in a dual Communicator. Cellular channel is the secondary path.
Programming Options 2G Alarm Communicator Installlation Manual Enter the IP address for DNS Server 1. Format is 4 fields, each field is a 3 digit decimal. Valid range: 000-255. NOTE: If no value is programmed and DHCP is used, the DHCP Server will configure the address. If an address is programmed and DHCP is used, the address that you program will be used instead of the DHCP address. [008] DNS Server IP 2 Programming this Section is not permitted on a UL/ULC listed system. Default (000.000.000.
2G Alarm Communicator Installlation Manual Programming Options Table 8: World Wide Time Zones HEX Value 11 15 -8 -7 -6 Std Abbrev Location PST Pacific Standard Time PST Pitcarirn Standard Time CIST HEX Value Offset Hours Std Abbrev Location 4B 6.
Programming Options 2G Alarm Communicator Installlation Manual Table 8: World Wide Time Zones 41 3.
2G Alarm Communicator Installlation Manual Communications Reporting Codes Table 8: World Wide Time Zones CAST Chinese Atlantic Standard Time WKST West Kazakhstan Standard Time PKT Pakistan Time YEKT Yekaterinburg Time UZT Uzbekistan Time TMT Turkmenistan Time TJT Tajikistan Time TFT French Southern and Antarctic Time MVT Maldives Time MAWT Mawson Time KGT Kyrgyzstan Time HMT Heard and McDonald Island Time DAVT Davis Time Offset Hours Std Abbrev Location ft_ _d _I C C 5 HEX
System Test Options [026 - 029] 2G Alarm Communicator Installlation Manual SYSTEM TEST OPTIONS [026 - 029] Test Transmissions to Primary Receiver, with Backup to Secondary Receiver: Set Ethernet Section [026] to (FF); [027] to (00). Set Cellular Section [028] to (FF); [029] to (00). • If the test transmission fails to the primary receiver it will backup to the secondary receiver. • If the test transmission fails to the secondary receiver an FTC trouble will be generated.
2G Alarm Communicator Installlation Manual Ethernet Receiver 1 Options Table 11: Panel Tamper Alarm Restore Event SIA Identifier SIA Reporting Code Contact ID Qualifier Contact ID Event Code Contact ID Reporting Code Contact ID User/Zone [033]Comm. FW Update Begin LB 00 1 9 03 002 [034]Comm.
Ethernet Options 2G Alarm Communicator Installlation Manual [112] Ethernet Receiver 2 DNIS Default (000000) The DNIS is used in addition to the account code to identify the Communicator module at the central station. Valid range: 000000 099999. Value is entered as leading 0 followed by the 5 digit DNIS. Format is BCD. NOTE: Each Ethernet/Cellular receiver must be programmed with a unique DNIS. [113] Ethernet Receiver 2 Address Default (000.000.000.
2G Alarm Communicator Installlation Manual Cellular Receiver 2 Options [203] Cellular Receiver 1 Address Default (000.000.000.000) Enter the Cellular Receiver 1 IP address. This information will be provided by your central station system administrator. Each 3 digit segment of the address must be within a valid range of 000-255. NOTE: When a valid IP address has been entered, the Cellular is enabled and will communicate events over the Cellular channel.
Event Notification and Interactive Options 2G Alarm Communicator Installlation Manual [222] Cellular Login User Name Default ( ) Some network carriers require you to provide login credentials when connecting to an APN. Program your login User Name in this Section. Format is up to 32 ASCII characters. NOTE: This Section is not accessible via PC1616/PC1832/PC1864 keypad programming.
2G Alarm Communicator Installlation Manual SMS Notification Table 14: Event Notification Language Language Default Language Default Language Default Language Default English OFF Czech ON Greek ON Latvian OFF Spanish OFF Finnish OFF Turkish OFF Lithuanian OFF Portuguese OFF German OFF Croatian ON Ukrainian ON French OFF Swedish OFF Hungarian ON Slovakian OFF Italian OFF Norwegian OFF Romanian OFF Serbian ON Dutch OFF Danish OFF Russian ON Estonian OFF
Zone Label Programming 2G Alarm Communicator Installlation Manual ZONE LABEL PROGRAMMING [401] - [464] Zone 1 - 64 Label Default (Zone n); Where n is a Zone number from 1 - 64. Zone Labels are up to 32 ASCII characters. Labels are used to identify the Zone for notification messages that apply to a specific Zone. The label language is specified in Section [009]. Zone labels are numbered 1 - 64 and Zones are numbered 1-128. No labels are assigned to Zones 65-128.
2G Alarm Communicator Installlation Manual Communicator Event Label Programming Table 15: Panel Event Labels Event [Section] Label Default Label Event [Section] Label Default Label [557] General System Trouble [General System Trouble] [558] General System Trouble Restore [General System Trouble Restore] [559] AC Line Trouble [AC Power Failure] [560] AC Line Trouble Restore [AC Power Restore] [561] Battery Trouble [Battery Trouble] [562] Battery Trouble Restore [Battery Restore] [563] Bell
SMS Command and Control Response 2G Alarm Communicator Installlation Manual [604] Disarm Default (Disarm); Send this command to the system to disarm. It may be followed by a Partition Label or partition number and Access Code. [605] - [608] Activate Command Output 1 - 4 Default (Activate Command Output n); Where n is a number from 1 - 4. Send this command to the system to activate a command output. It may be followed by a Partition Label or partition number and Access Code.
2G Alarm Communicator Installlation Manual SMS Command and Control Response [626] System Night Armed Default (Night Armed); This label will be included in the response to a status request command if a partition is night armed. [627] System Disarmed Ready Default (Disarmed Ready); This label will be included in the response to a status request command if a partition is disarmed and is ready to arm.
SMS Command and Control Response 2G Alarm Communicator Installlation Manual OFF: Flow Control is disabled. [5]-[8]Reserved Default (OFF) [663] Interactive Feature Toggle Option This feature is used to select the interactive feature services. Bit [1] Reserved. {Interactive over serial port (default Enabled) - on -SM manual} Bit [2] Interactive over cellular radio (default Disabled) Bit [3] Future use Bit [4] Default (ON) ON: Interactive over Cellular radio is Primary.
2G Alarm Communicator Installlation Manual SMS Command and Control Response [676] Life-Style Zone 33 - 40 Toggle Options The default for each Life-Style Zone Toggle is ON. TOGGLE ZONE 01 33 02 34 03 35 04 36 05 37 06 38 07 39 08 40 03 43 04 44 05 45 06 46 07 47 08 48 04 52 05 53 06 54 07 55 08 56 04 60 05 61 LC Table 22: Life-Style Zone 33 - 40 Toggle [677] Life-Style Zone 41 - 48 Toggle Options The default for each Life-Style Zone Toggle is ON.
SMS Command and Control Response 2G Alarm Communicator Installlation Manual [685] Notification Zone 25 - 32 Toggle Options The default for each Notification Zone Toggle is OFF. Table 29: Notification Zone 25 - 32 Toggle TOGGLE ZONE 01 25 02 26 03 27 04 28 05 29 06 30 07 31 08 32 06 38 07 39 08 40 06 46 07 47 08 48 06 54 07 55 08 56 06 62 07 63 08 64 [686] Notification Zone 33 - 40 Toggle Options The default for each Notification Zone Toggle is OFF.
2G Alarm Communicator Installlation Manual SMS Command and Control Response 29 00 82 18 R 00 1_ N O VA _T L2 55 G S_ G S2 05 5_ V .2 .5 X_ IM _E N G _N A_ U L_ U LC _F C C _I C _d ft_ 03 Enter the Domain Name as 32 ASCII characters. This information will be provided by your central station system administrator. [698] Interactive over 2G local event report port (UDP Port) Default (3076) This Section is used to program the DUP port number used the communicator.
System Information (Read Only) 2G Alarm Communicator Installlation Manual RECEIVER DIAGNOSTIC TESTING [901] Diagnostic Test Transmission [1] Ethernet 1 (OFF). [2] Ethernet 2 (OFF). [3] Cellular 1 (OFF). [4] Cellular 2 (OFF). [5],[6],[7],[8] Reserved (OFF). This Section may be used by the installer to force the Communicator to send an immediate test transmission to specific receivers, to verify that the communications paths are available.
2G Alarm Communicator Installlation Manual Communicator Troubleshooting Communicator Troubleshooting [984] Communicator Status The communicator status sections are intended to provide the installer with real time status of communicator’s functionality, operational readiness, failures, and potential malfunctions that may affect flawless operation of the communicator and its primary function of sending signal to the central station in case the monitored event occurs.
Communicator Troubleshooting 2G Alarm Communicator Installlation Manual Table 35: Radio Initialization Status - 1-8 bits completion Bit Not Completed Completed 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 For example the radio initialization status code 12345--- indicates that Radio has been powered up, it has received SMS signal from C24, the radio has been reset, the radio is attached to the network, and Radio 1 has been initialized. This code could be followed with...
2G Alarm Communicator Installlation Manual Communicator Troubleshooting Communicator Troubleshooting The status code for the radio signal strength, its typical troubles, possible causes and troubleshooting instructions is displayed in the table below. Table 37: Radio Signal Strength Signal Strength CSQ Level No Signal 0 ON OFF OFF -108.
System Options 2G Alarm Communicator Installlation Manual ETHERNET/CELLULAR PROGRAMMING WORKSHEETS SYSTEM OPTIONS [020] Time Zone [001] Ethernet IP Address Default (CAFE) Valid range: 0000 - FFFF. |____|____|____|____| Default (000.000.000.000) [022] Communications Format |____|____|____||____|____|____||____|____|____|____|____|____| Default (04) Program 03 (CID), 04 (SIA). [002] Ethernet IP Subnet Mask Default (255.255.255.
2G Alarm Communicator Installlation Manual Ethernet Receiver 2 Options ETHERNET RECEIVER 2 OPTIONS [212] Cellular Receiver 2 DNIS [111] Ethernet Receiver 2 Account Code Default (000000) Valid range: 000000 - 0FFFFF. Default (0000000000) Valid range: 0000000001 - FFFFFFFFFE. |____|____|____|____|____|____| |____|____|____|____|____|____|____|____|____|____| [213] Cellular Receiver 2 Address [112] Ethernet Receiver 2 DNIS Default (000.000.000.
[634] Error Code 2G Alarm Communicator Installlation Manual |____| [2] Interactive over cellular radio. Defeault (OFF) [685] Notification Zone 25 - 32 Toggle Options |____| [3] Future |____|____|____|____|____|____|____|____| 25 26 27 28 29 30 31 32 |____| [4] Interactive over Cellular radio is Primary Default (ON).
2G Alarm Communicator Installlation Manual System Information (Read Only) [705] Interactive over 2G server 2 UDP port Default ( ) [901] Diagnostic Test Transmission |___| [1] Ethernet 1 Default (OFF). ||____|____|____| |____|____|____| |____|____|____| |____|____|____| |___| [2] Ethernet 2 Default (OFF). [706] Interactive over 2G server 2 APN Default ( ) |___| [3] Cellular 1 Default (OFF). |___| [4] Cellular 2 Default (OFF).
End User Licence Agreement 2G Alarm Communicator Installlation Manual END USER LICENCE AGREEMENT IMPORTANT - READ CAREFULLY: DSC Software purchased with or without Products and Components is Copyrighted and is purchased under the following license terms: .2 .5 X_ IM _E N G _N A_ U L_ U LC _F C C _I C _d ft_ 03 Termination - Without prejudice to any other rights, DSC may terminate this EULA if You fail to comply with the terms and conditions of this EULA.
2G Alarm Communicator Installlation Manual Limited Warranty LIMITED WARRANTY 29 00 82 18 R 00 1_ N O VA _T L2 55 G S_ G S2 05 5_ V ft_ _d _I C C _F C .2 .5 X_ IM _E N G _N A_ U L_ U LC International Warranty The warranty for international customers is the same as for any customer within Canada and the United States, with the exception that Digital Security Controls shall not be responsible for any customs fees, taxes, or VAT that may be due.
FCC Compliance Statement CAUTION: Changes or modifications not expressly approved by the Digital Security Controls could void your authority to use this equipment. This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.