User's Manual
13
Figure 3 - Telephone Connection
Figure 4 - Power Supply and Supervision Wiring Diagram
The following wiring diagrams (Figures 5 to 8) are examples of ULC Listed Fire Monitoring Installation
connections.
3G3070 Wiring Diagrams - statFmHere-8/9-09.00
RED (R)
GREEN (T)
GRAY (R)
BROWN (T)
RJ-31X
RING
TIP
CONTROL PANEL
Incoming
Phone line
Handset
RI
TI
TI
RI
TIP
RING
4
321
5
3G3070
TIP T1 R1
RNG
(BLK/WHT) +13.8VDC
(BLK ) GND
Control
Panel
EOL
Resistor
See Note 3
DSC
RM-2
RELAY
NC
C
NO
ZONE
TERMINALS
(See Note 1)
- +
+12VDC
GND
CONTROL PANEL
Aux Power
+ -
DSC
Supervision
Relay
See Note 2
19
18
171614
20
15
12
11
1097
13
86
19
Z4
Z3Z2
COM
20
Z1
12
AUX
+
PGM
3
PGM
1
13
PGM
4
COM
TAMPER
3G3070
PGM
3
DC IN
+ -
KSAD1380100W1US
Power Adaptor
NOTES
1.
Program the Zone/Point as “Supervisory” type
with keypad only annunciation when in Alarm.
Do
NOT use a point that is normally used for
2-Wire Smoke detectors.
2.
The power Supervision relay,
RM-2
is only used
when the 3G3070 is
not
powered by the control
panel. When the Radio is powered by the control
panel the relay is not required since a loss of input
power will generate a signal to the CMC.
3.
Output 4 on the 3G3070 must be set as “Active
High” (default).
4.
When powering the 3G3070 Radio by an
Auxiliary Power supply that has its own backup
battery, insert JP3 jumper on the radio and remove
the 1.2AH battery that came with the radio.