3G3070 3G-GPRS INTERFACE INSTALLATION MANUAL V3.5 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully read.
TABLE OF CONTENTS - NEW 3G3070 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Identification of Parts . . . . . . . . . . . . . . . . . . . . . .
IMPORTANT The equipment is fixed, wall-mounted and shall be installed in the position specified in these instructions. The equipment enclosure must be fully assembled and closed, with all the necessary screws/tabs and secured to a wall before operation.
Introduction The 3G3070 is a wireless communicator that sends alarm system information to an SG-System III, SGSystem II, or SG-System I receiver through a GSM/GPRS wireless network. This wireless communicator can be used with UL/ULC Listed compatible control units, as indicated in the manufacturer's installation instructions. NOTE: The 3G3070 is designed to work with the Contact ID communication format as described in SIA DC05 Standard.
Identification of Parts Figure 1 - Parts 2 1 14 54 16 17 6 3 4 LOCK JP3 OPEN OFF ON NOTE: For UL/ULC installations, connections between the alarm control panel outputs (telephone interface Tip/Ring, output relay contacts) and 3G3070 inputs (Tip/Ring, Z1-Z4) shall be run in a mechanical protective conduit within 20ft (6m) of one another and in the same room.
This equipment 3G3070 is fixed and shall be installed by Service Persons only (Service Person is defined as a person having the appropriate technical training and experience necessary to be aware of hazards to which that person may be exposed in performing a task, and of measures available to minimize the risks to that person or other persons). It shall be installed and used within an environment that provides the pollution degree max 2, over voltages category II, in non-hazardous, indoor locations only.
Installing the 3G3070 CONNECT 24 Enrolment Information Only authorized dealers can enrol a 3G3070 with CONNECT 24. Dealer application forms and additional information on the CONNECT 24 Voice Response Unit can be found at the CONNECT 24 website www.connect24.com. Please contact CONNECT 24 at the number below for assistance: USA 1-888-251-7458 CANADA 1-888-955-5583 NOTE: Steps 1 and 2 should be completed before turning on the 3G3070 unit.
Tamper (12-13) - These terminals are connected in series to the Tamper switch [10]. They will close when the cabinet is properly closed, and will open when the front cover is removed. Z1-Z4 (15-16-17-18) Programmable Inputs - These terminals can be set up to trigger events. Refer to ‘Inputs’ for details. 12V (19), COM (20) Device Power Supply - hese terminals must be connected to a rated power supply.
Operating Principles Simulated Landline Mode The simulated landline provides the alarm control panel (with dialer interface) with a back up line in the event of PSTN line trouble. If the voltage on the landline terminals (TIP/RNG) drops below 2.8V for a period of between 10 seconds and 45 seconds - depending on the device connected to the T1/R1 terminals- the 3G3070 switches the connected telephone device to the GSM network.
NOTE: For UL/ULC installations, connections between alarm panel outputs and 3G3070 inputs must be run in protective mechanical conduits. To reduce interference with the antenna, it is recommended that the metal conduit is not connected to the knock-outs in the top of the cabinet. Outputs The 3G3070 has four programmable outputs to activate in response to the associated events. Refer to the 3G3070 Wiring Diagram (Figure 2) at the back of this manual.
Low Power Radio Shutdown When the battery voltage reaches the low battery threshold of 10.5V, the unit turns off the radio to prevent unnecessary network registrations. In this state, the unit does not communicate any events. Radio shutdown is indicated by the LEDs as follows: • for 1 second -- red is on, yellow is off, green 1 is off, and green 2 is off. • for 1 second -- red is off, yellow is on, green 1 is on, and green 2 is on.
Yellow Light Status What It Means: GSM Status/Communication Indicator Yellow Light ON • When used as the primary communicator, the yellow light will always be ON. • When used as a backup communicator, the yellow light will be ON when there is a no phone line connected to the 3G3070 TIP and RING, or the line voltage goes below 2.8VDC. Yellow Light OFF • Indicates a good phone line is connected to the 3G3070. (more than 2.8 VDC detected across the 3G3070 TIP and RING terminals).
The Red light will flash to indicate various trouble conditions outlined previously. If multiple trouble conditions are present, the red light will flash according to the highest priority trouble. For example, if both a 3G3070 low battery trouble (one flash) and an insufficient signal strength trouble (four flashes) are present; the red light will flash one time. Once the 3G3070 low battery trouble condition is corrected, the red light will then begin flashing four times.
General Information Enrolling a 3G3070 • The 3G3070 can be enrolled by going through the GVRU voice prompt, and completing the activation of the SIM card, and the initialization of the 3G3070 • The 3G3070 can also be enrolled using the Connect 24 website (www.connect24.com) SIM card activation period • A SIM card can take up to 24 hours to be activated by the provider. However, it typically takes less than an hour for the SIM card to be activated Checking SIM status • Go to www.connect24.com and login.
GROUND CONNECTION RJ-45 Earth-ground Ground wire from building electrical installation 2 LE 3 R I N G Optional use of PGM output (See Programming) 12 For ULC Fire Monitoring installations fire alarm signals shall be sent simultaneously over POTS line (using the dialler) and over the GSM network (using 3G3070). Connect alarm output from control panel (PGM) to the input on the 3G3070 that is programmed as a Fire Alarm Input.
3G3070 Wiring Diagrams - statFmHere-8/9-09.00 Figure 3 - Telephone Connection CONTROL PANEL RJ-31X RING TIP TI TIP RNG T1 RI RI 5 4 3 BROWN (T) TI RING TIP 2 GRAY (R) RED (R) GREEN (T) 1 Incoming Handset Phone line 3G3070 R1 Figure 4 - Power Supply and Supervision Wiring Diagram CONTROL PANEL ZONE TERMINALS (See Note 1) Aux Power + + 2. The power Supervision relay, RM-2 is only used when the 3G3070 is not powered by the control panel.
3G3070 Wiring Diagrams Figure 5 - Fire Alarm Control Unit and GSM Transmitter Wiring Diagram for Fire Alarm Control Unit (with dialler) and GSM Transmitter (Passive Communication System) Fire Alarm Control Unit AUX Power (12V/700mA) GSM Transmitter GSM Network GPRS (IP Data) GS3055-I 3G3070 TIP/RING T1/R1 TIP/RING PSTN Zone Input Zone Inputs Outputs Fire Trouble PGM4 Output RM1C ULC Relay 3G3070 cabinet AC Input NOTES: - Power for 3G3070 shall be provided from Fire Alarm Control Unit or separ
3G3070 Wiring Diagrams Figure 7 - DSC Subscribers’ Unit Fire and GSM Transmitter Mounted Remotely Alternate Wiring Diagram for DSC Subscribers’ Unit Fire and GSM Transmitter Passive Communication System -Using Phone Line Supervision Relay Fire Alarm Control Unit DSC Subscribers’ Unit Fire Outputs Fire Supervisory Trouble Zone Inputs AUX Power 12V/700mA PSTN T1/R1 Zone Input TIP/RING PGM1 PGM4 PGM1 RM1C ULC Relay RM1C ULC Relay RM1C ULC Relay PC5003C PC4050CR cabinet AC Input GSM Network GPRS (
3G3070 Wiring Diagrams Figure 8 -Connection Details for GSM Supervision Relay and Redundant Fire Alarm Transmission Connection Details for GSM Supervision Relay & Redundant Fire Alarm Transmission 3G3070 1 2 LE 3 4LI 5 6 O1 7 O2 8 O3 9 O4+OC 10 11 12 AS 13 14 15 L116L217L3 18 L4 1912V20 Z1 15Z216Z317 Z4 DC 20 IN COM PGM411 AUX+ TAMPER 7 PGM2 8 PGM3 9 10 18+19 3 4T1 5R1 6 PGM1 12 13 COM 14 1 TIP 2 RNG GSM Supervision Relay 5.
3G3070 Wiring Diagrams Figure 9 - Connection Details for GSM Supervision Relay, Phone Line Supervision and Redundant Fire Alarm Transmission Connection Details for GSM Supervision Relay, Phone Line Supervision Relay and Redundant Fire Alarm Transmission 3G3070 2 LE 3 4LI 5 3 4T1 5R1 2 RNG 1 TIP 1 6 O1 7 O2 8 O3 9 O4+OC 10 11 12 AS13 14 15 L116L217L3 18 L4 1912V20 COM6 PGM1 PGM411 AUX+ TAMPER Z1 15Z216Z317 Z4 DC 20 IN 7 PGM2 8 PGM3 9 10 18+19 12 13 COM 14 Redundant Fire Alarm Initiation 5.
IMPORTANT READ CAREFULLY: DSC Software purchased with or without Products and Components is copyrighted and is purchased under the following license terms: • This End User License Agreement ("EULA") is a legal agreement 3. COPYRIGHT between You (the company, individual or entity who acquired the Software and any related Hardware) and Digital Security Controls, a division of Tyco Safety Products Canada Ltd.
FCC COMPLIANCE STATEMENT CAUTION: Changes or modifications not expressly approved by Digital Security Controls could void your authority to use this equipment. This equipment generates and uses radio frequency energy and if not installed and used properly, in strict accordance with the manufacturer's instructions, may cause interference to radio and television reception.
Limited Warranty Digital Security Controls warrants the original purchaser that for a period of twelve months from the date of purchase, the product shall be free of defects in materials and workmanship under normal use. During the warranty period, Digital Security Controls shall, at its option, repair or replace any defective product upon return of the product to its factory, at no charge for labour and materials.