[025] Radio Activation Restore
Default (FF);
Program 00 to disable this event or FF to enable. This event will occur after any successful Connect24 programming session.
System Test Options [026 - 029]
Test Transmissions to Primary Receiver, with Backup to Secondary Receiver:
Set Ethernet Section [026] to (FF) and Section [027] to (00). Set Cellular Section [028] to (FF) and Section [029] to (00).
If the test transmission fails to the primary receiver it will backup to the secondary receiver.
If the test transmission fails to the secondary receiver an FTC trouble will be generated.
Test Transmission Unique to Primary and Secondary Receivers:
Set Ethernet Section [026] to (FF) and Section [027] to (FF). Set Cellular Section [028] to (FF) and Section [029] to (FF).
The module will send periodic test transmissions to each receiver independently, with no backups.
If the test transmission fails to any of the programmed receivers, an FTC trouble will be generated.
Alternate Test Transmission
Alternate Test Transmission can be enabled or disabled in Section [005] Toggle Option [7].
[026] Ethernet 1 Transmission
Default (FF);
Program 00 to disable this event transmission or FF to enable. See System Test Options (above) for details on settings.
[027] Ethernet 2 Transmission
Default (00);
Program 00 to disable this event transmission or FF to enable. See System Test Options (above) for details on settings.
[028] Cellular 1 Transmission
Default (FF);
Program 00 to disable this event transmission or FF to enable. See System Test Options (above) for details on settings.
[029] Cellular 2 Transmission
Default (00);
Program 00 to disable this event transmission or FF to enable. See System Test Options (above) for details on settings.
NOTE: Interval (in minutes) between periodic tests is programmed in Section [125] (Ethernet) and Section [225] (Cellular).
[030] FTC Restore
Default (FF);
Program 00 to disable or FF to enable. This event will occur when an FTC Trouble on the system restores.
[031] Panel Tamper Alarm
Default (FF);
Program 00 to disable this event transmission or FF to enable. This event will occur when a Panel Tamper occurs on the system.Setting
this option to 00 will disable monitoring of the tamper switch. See Table 12 for SIA and CID reporting codes.
[032] Panel Tamper Alarm Restore
Default (FF);
Program 00 to disable this event transmission or FF to enable. This event will occur when a Panel Tamper event on the system restores.
See Table 9 for SIA and CID reporting codes.
ETHERNET RECEIVER 1 OPTIONS
(TL255-SM/TL2553G-SM only)
[101] Ethernet Receiver 1 Account Code
Default (0000000000);
The account code is used by the central station to distinguish between transmitters. This account code is used when transmitting heart-
beat signals to the central station receiver. Signals received from the control panel will use the control panel account number. Valid
range: 0000000001-FFFFFFFFFE. Programming this Section as all 0 or all F will cause a Module Configuration Trouble (yellow
LED=12 flashes).
NOTE: If Ethernet Receiver 1 and Cellular Receiver 1 are programmed as the same receiver (IP and port number are identical), Ether-
net Receiver 1 account code will be used.
[102] Ethernet Receiver 1 DNIS
Default (000000);
The Dialled Number Information Service (DNIS) is used in addition to the Account Code to identify the Communicator module at the
central station. Valid range: 000000 - 099999. Value is entered as a leading 0 followed by the 5 digit DNIS. Format is Binary Coded
Decimal (BCD).
NOTE: Each Ethernet/Cellular receiver must be programmed with a unique DNIS.
Table 9: Panel Tamper Reporting Codes
Event
SIA
Identifier
SIA
Reporting Code
CID
Qualifier
CID
Event Code
CID
Reporting Code
CID
User/
Zone
Panel Tamper ES 001 1 1 45 001
Panel Tamper Restore EJ 001 3 1 45 001