User's Manual

3G Alarm Communicator Installlation Manual Encryption
7
NOTE: Following initial installation, you can log in to the Connect24 website at any time to re-configure the Communicator remotely,
using the account created for this installation. For more information, refer to the Connect24 website.
Before leaving the installation site, the Communicator TL2553G or TL255 shall be connected via an APPROVED (acceptable
to the local authorities) Network Interface Device (NID) (e.g., for UL Installations, U60950 listed NID). All wiring shall be per-
formed according to the local electrical codes.
ENCRYPTION
The Communicator uses 128 Bit AES Encryption. Encryption can only be enabled from the monitoring station receiver. Each receiver
can independently have encryption enabled or disabled. When encryption is enabled, the central station will configure the device to
encrypt communications the next time the Communicator module performs a communication to that receiver.
NOTE: Packets will start being encrypted only after the next event is sent to that receiver, or if the unit is restarted.
NOTE:
NOTE:
NOTE: The Alarm Communicator is installed in the
SCW prior to shipment by Digital Security Controls
(DSC). The Factory Installation includes insertion of
the SIM card. The SCW should not be mounted in its
final location without performing a Communicator
Test to ensure adequate HSPA/3G coverage for the
3G2055 and TL2553G Alarm Communicators
INSTALLATION LOCATION
The Communicator shall be installed in an indoor loca-
tion, within the Self Contained Wireless (SCW) Con-
trol Panel, and near the main entrance, on the main
floor of the dwelling or other prefered place.
This HSPA/3G/Ethernet Communicator shall be
installed by Service Personnel only. (Service Person is
defined as a person having the appropriate technical
training and experience necessary to be aware of haz-
ards to which that person may be exposed in perform-
ing a task and can also take measures to minimize the
risks to that person or other persons). The Communica-
tor shall be installed and used within an environment
that provides the pollution degree max 2, over voltages
category II, in non-hazardous, indoor locations only. This manual shall be used with the Installation Manual of the alarm control panel
which is connected to the HSPA/3G/Ethernet Communicator. All instructions specified within the panel manual must be observed.
All the local rules imposed by local electrical codes shall be observed and respected during installation.
INSTALLING CAT 5 CABLE (TL2553G/TL255 ONLY)
A Category 5 (CAT 5) ethernet cable must be run from a source with Ethernet/Internet connectivity to
the Communicator module, inside the Self Contained Wireless Control Panel cabinet. The Communi-
cator end of the cable must have an RJ-45 plug, which connects to the Communicators RJ-45 jack.
All requirements for installation of CAT5 ethernet cable must be observed for correct operation of the
Communicator, including, but not limited to, the following:
Do NOT strip off cable sheathing more than required for proper termination.
Do NOT kink/knot cable.
Do NOT crush cable with cable ties.
Do NOT untwist CAT5 pairs more than 1.2cm (½”).
Do NOT splice cable.
Do NOT bend cable at right angles or make any other sharp bends.
NOTE: CAT5 specification requires that any cable bend must have a minimum 5 cm (2 in.) bend
radius. Maximum length of CAT 5 cable is 100m (328 ft.).
NOTE: The Ethernet cable shall not be visible when the installation is complete unless the install is a
surface mount installation
COMMUNICATOR CONFIGURATION WITH SCW
Figure 1: UA580 PCB Connection Points .
RJ-45
SIM Card
PC-LINK
Use CAT 5 Cable Only
DG009640
Ribbon Interface
(16 Pins)
RJ-45 Connector
DG0009635
Figure 2: RJ-45 Pinout