User's Manual
19
[024] Panel Absent Trouble Restore
Default (FF)
Program 00 to disable this event or FF to enable. This event will occur when communications with the control panel
have resumed.
[025] Radio Activation Restore
Default (FF)
Program 00 to disable this event or FF to enable. This event will occur after any successful Connect24 program-
ming session.
System Test Options [026 - 029]
Test Transmissions to Primary Receiver, with Backup to Secondary Receiver:
Set Ethernet Section [026] to (FF); [027] to (00). Set GPRS Section [028] to (FF); [029] to (00).
• If the test transmission fails to the primary receiver it will backup to the secondary receiver.
• If the test transmission fails to the secondary receiver an FTC trouble will be generated.
Test Transmission Unique to Primary and Secondary Receivers:
Set Ethernet Section [026] to (FF); [027] to (FF). Set GPRS Section [028] to (FF); [029] to (FF).
• The module will send periodic test transmissions to each receiver independently, with no backups.
• If the test transmission fails to any of the programmed receivers, an FTC trouble will be generated.
Alternate Test Transmission
Alternate Test Transmission can be enabled or disabled in Section [005] Toggle Option [7].
[026] Ethernet 1 Transmission
Default (FF)
Program 00 to disable this event transmission or FF to enable. See System Test Options (above) for details on settings.
[027] Ethernet 2 Transmission
Default (00)
Program 00 to disable this event transmission or FF to enable. See System Test Options (above) for details on settings.
[028] GPRS 1 Transmission
Default (FF)
Program 00 to disable this event transmission or FF to enable. See System Test Options (above) for details on settings.
[029] GPRS 2 Transmission
Default (00)
Program 00 to disable this event transmission or FF to enable. See System Test Options (above) for details on settings.
NOTE: The time interval (in minutes) between periodic tests is programmed in Section [125] (Ethernet)
and Section [225] (GPRS).
[030] FTC Restore
Default (FF)
Program 00 to disable this event transmission or FF to enable. This event will occur when an FTC Trouble on the
system restores.
[031] Panel Tamper Alarm
Default (FF)
This event will occur when a Panel Tamper is detected during the Entry Delay time. The panel shall notify the
communicator immediately, creating a Priority Tamper Alarm condition. Setting this option to 00 will disable
monitoring of this condition. See Table 11 for SIA and CID reporting codes. Program 00 to disable this event
transmission or FF to enable event transmission.
[032] Panel Tamper Alarm Restore
Default (FF)
Program 00 to disable this event transmission or FF to enable. This event will occur when a Panel Tamper event on
the system restores. See Table 11for SIA and CID reporting codes.
Ethernet Receiver 1 Options
[101] Ethernet Receiver 1 Account Code
Default (0000000000)
The account code is used by the central station to distinguish between transmitters. This account code is used
when transmitting heartbeat signals to the central station receiver. Signals received from the control panel will use
the control panel account number. Valid range: 000000000
1
-FFFFFFFFF
E
.
Programming this Section as all
0
or all
F
will cause a Module Configuration Trouble (yellow LED=12 flashes).
NOTE: If Ethernet Receiver 1 and GPRS Receiver 1 are programmed as the same receiver (IP and port
number are identical), Ethernet Receiver 1 account code will be used.
Table 11: Panel Tamper Reporting Codes
Event
SIA
Identifier
SIA
Reporting Code
CID
Qualifier
CID
Event
Code
CID
Reporting
Code
CID
User/
Zone
Panel Tamper ES 001 1 1 45 001
Panel Tamper Restore EJ 001 3 1 45 001