User's Manual
8
h. Insert the PC-LINK connector into the Communicator’s PC-LINK socket. (Black wire on Pin 1 on the
Communicator).
RS-232 Connection for Customer Furnished Equipment
4. Run a 3 wire RS-232 cable from the CFE to the Panel and Communicator.
5. Terminate the wires on the Communicator, as follows:
a. Connect the TX wire to the TX terminal on the Communicator.
b. Connect the RX wire to the RX terminal on the Communicator.
c. Connect the ground wire to the GND terminal on the Communicator.
d. Connect the other end of the RS-232 cable as required by the CFE installation guide.
Install Network Cable (TL260-RS/TL260GS-RS only)
6. Route the CAT 5 Ethernet cable through back of the panel and plug it into the Communicator’s RJ45 jack.
Before leaving the premises the Ethernet communication lines must first be connected to an approved
(acceptable to local authorities) type NID, (UL installations, UL 60950 listed NID, for ULC installations
CAN/CSA C22.2. No. 60950-1 Certified NID). All wiring shall be performed according to the local electri-
cal codes.
Figure 3 Communicator Wiring Diagram
DG00959
3
AUDIO/ DEFAULT
DSC
UA585
PC-LINK
PC- LI NK
GND
TL260-RS
TL260GS-RS
GS2060-RS
AC
AC
Z1 COM Z2 Z3 COM Z4 Z5 COM Z6 Z7 COM Z8
AUX+
BELL +
PGM1 PGM3
RING
T-1
PC1616/1832/1864
GSM Radio
RX 1 & RX 2
+
-
UA503
1
To external antenna
Input Ratings from Bell +:
+11.1V ~ +12.6 VDC
100mA standby; 400mA alarm
DSC Panel min power requirements:
- 16 VAC 40 VA transformer;
- 12 VDC 7Ah battery
+
-
External Bell/Siren
Black
Black
Jumper pins 4 and 5
to reset.
L
o
c
k
1
GRN
RS-232
To External Device
Maximum cable length
16 m (50 ft)
From NID
(GS2060-RS/TL260GS-RS)
Use only CAT5
Supervised
RJ-45
YEL
COM
PWR
GRN
YEL
TIP
R-1
BLK
RED
AUX -
BELL -
EGND
TX+
GND
RX+
SHLD
Green
Yellow
SIM
Network Link
(TL260-RS only)
YELLOW
PGM2 PGM4
Maximum cable length
100 m (328 ft)
PWR
REV 0 1
(GS2060-RS
TL260GS-RS only)