User's Manual

Table Of Contents
15
TL260GS/GS2060 Communicator Wiring Diagram
Optional Antenna Kits
The PC1616 / PC1832 / PC1864 cabinet contains an external GSM radio antenna. If the required GSM signal strength cannot be
achieved using this antenna, the following selection of GSM extension antenna kits are available to the installer:
GS15-ANTQ - 4.57m (15’) Internal Antenna Extension Kit (suitable for internal mounting only)
GS25-ANTQ - 7.62m (25’) External Antenna Extension Kit (suitable for external mounting only)
GS50-ANTQ - 15.24m (50’) External Antenna Extension Kit (suitable for external mounting only)
Specific instructions for the installation of each extension antenna are included with each kit.
Installation with PC9155 Control Panel (models TL265GS and GS2065)
1. Attach the Communicator to the inside of the PC9155 control panel cabinet if not already present.
NOTE: Install the TL265GS / GS2065 before turning on the system.
NOTE: Before inserting or removing the SIM card, please ensure the unit is turned off.
Separate the cabinet covers and place the Communicator in the space provided.
Attach the 5-pin PC-Link cable to the panel.
Locate the Ethernet jack on the panel and plug in the cable.
Locate the 2-terminal block (beside the Ethernet jack) labelled GND SHLD and attach to the circuit ground.
Before leaving the premises
the Ethernet communication
lines must first be connected to
an approved (acceptable to
local authorities)type NID
device, (UL installations, UL
60950 listed NID, for ULC
installations CAN/CSA C22.2.
No. 60950-1 Certified NID).
D G 009074
Network Connection
(Available only for model
TL260GS) Use only CAT5
cable (300ft/100m max.)
Supervised
AUDIO/DEFAULT
DSC
UA557
PC-LINK
PC-LINK
GND
PW R
PW R GN D G ND
SHLD
TL260GS / GS2060
AC AC RED BLK YEL GRN Z1 COM Z2 Z3 COM Z4 Z5 COM Z6 Z7 COM Z8
AUX+ BELL+
AUX-
BELL-
PGM1 PGM3
EGND
TIP T-1
PGM2 PGM4
RING R-1
PC1616/1832/1864
Radio
SIM Card
Holder
+
-
WARNING! All connections to the
TL260GS/GS2060 module are power
limited. Do not route any wiring over the
circuit boards. Maintain at least 1”
(25.4mm) separation between circuit
board and wiring. A minimum of 1/4”
(7mm) separation must be maintained at
all points between non-power limited
wiring and power limited wiring.
Wiring the TL260GS/GS2060 Module to a PC1616/1832/1864
- Remove the circular knock out in the top right-hand corner of the cabinet and mount
the TL260GS/GS2060 module in place (secure using screws supplied).
- Attach the TL260GS/GS2060 antenna to the unit.
- With both the AC and battery disconnected from the DSC control panel, wire the
supplied PC-Link cable.
- Wire the Bell+ of the control panel to the TL260GS/GS2060 PWR terminal.
- Wire the AUX- on the control panel to the TL260GS/GS2060 GND.
- Apply AC and DC to the main control panel, the TL260GS/GS2060 and the
PC1616/1832/1864 should power up.
- Perform the necessary programming.
- Call the Connect 24 VRU to activate your account.
NOTE: If a Bell/Siren is not being used, wire the Bell/Siren terminals on the panel with
a 1K Ω resistor, then only wire the BELL+ to the BELL IN of the TL260GS/GS2060.
Connection the PC-Link Cable
- Insert the connector on the TL260GS/GS2060 with the black wire on Pin 1 of the
PC-Link header.
- Insert the other end of the cable on the PC1616/1832/1864 with the red wire on Pin 1
of the PC-Link header.
UA503
Input Ratings
(from PC-Link)
10V - 13.8 V
DC
100mA standby
400mA Alarm
DSC Panel minimum
power requirements
16 V
AC 40 VA transformer
12 VDC Ah battery
NOTE: For more details, refer to the
control, panel Installation Manual p/n
29007359.
NOTE: For ULC Commercial Fire
Monitoring applications, do NOT connect
any devices on the Bell+ terminal other
than the TL260GS/GS2060.
1
1
CON 4
See PC-Link wiring
instructions below
To external