Installation Manual
29
Appendix B - Zone Alarms/Restorals
Only SIA event code-zone # has been done. Connect24 does conversion from SIA to Contact ID. This has been done using
PC5020 v3.2 and Skyroute v2.4 test 11.
PGM2
Definition
Zone
Definition
Description
Skyroute
Transmission
Option Section
[22]
Full Reporting Generic Reporting
SIA (event code-zone #)
Contact ID
(event code-
zone#)
SIA (event
code-zone#)
Contact ID
(event code-
zone#)
- 01 Delay 1 1 (Alarm/Restoral) BA-XX / BH-XX
E130-0XX /
R130-0XX
BA-98 / BH-XX
E130-0098 /
R130-0XX
- 02 Delay 2 1 (Alarm/Restoral) BA-XX / BH-XX
E130-0XX /
R130-0XX
BA-98 / BH-XX
E130-0098 /
R130-0XX
- 03 Instant 1 (Alarm/Restoral) BA-XX / BH-XX
E130-0XX /
R130-0XX
BA-98 / BH-XX
E130-0098 /
R130-0XX
- 04 Interior 1 (Alarm/Restoral) BA-XX / BH-XX
E130-0XX /
R130-0XX
BA-98 / BH-XX
E130-0098 /
R130-0XX
- 05 Interior, Stay-Away 1 (Alarm/Restoral) BA-XX / BH-XX
E130-0XX /
R130-0XX
BA-98 / BH-XX
E130-0098 /
R130-0XX
- 06 Delay, Stay-Away 1 (Alarm/Restoral) BA-XX / BH-XX
E130-0XX /
R130-0XX
BA-98 / BH-XX
E130-0098 /
R130-0XX
- 07 Delayed 24 Hour Fire (Hardwired0 1 (Alarm/Restoral) FA-XX / FH-XX
E110-0XX /
R110-0XX
FA-98 / FH-XX
E110-098 /
R110-0XX
- 08 Standard 24 Hour Fire (Hardwired) 1 (Alarm/Restoral) FA-XX / FH-XX
E110-0XX /
R110-0XX
FA-98 / FH-XX
E110-098 /
R110-0XX
- 09 24 Hour Supervisory (LINKS) 1 (Alarm/Restoral) US-XX / UR-XX
E150-0XX /
R150-0XX
UA-98 / UR-XX
E140-098 /
R140-0XX
- 10 24 Hour Supervisor Buzzer 1 (Alarm/Restoral) UA-XX / UH-XX
E140-0XX /
R140-0XX
UA-98 / UH-XX
E140-098 /
R140-0XX
- 11 24 Hour Burglary 1 (Alarm/Restoral) BA-XX / BH-XX
E130-0XX /
R130-0XX
BA-98 / BH-XX
E130-0XX /
R130-0XX
- 12 24 Hour Hold-Up 1 (Alarm/Restoral) HA-XX / HH-XX
E122-0XX /
R122-0XX
PA-98 / HH-XX
E120-098 /
R122-0XX
- 13 24 Hour Gas 1 (Alarm/Restoral) GA-XX / GH-XX
E151-0XX /
R151-0XX
GA-XX / GH-XX
E151-0XX /
R151-0XX
- 14 24 Hour Heat 1 (Alarm/Restoral) KA-XX / KH-XX
E158-0XX /
R158-0XX
KA-XX / KH-XX
E158-0XX /
R158-0XX
- 15 24 Hour Medical 1 (Alarm/Restoral) MA-XX / MH-XX
E100-0XX /
R100-0XX
MA-98 / MH-XX
E100-0098 /
R100-0XX
- 16 24 Hour Panic 1 (Alarm/Restoral) PA-XX / PH-XX
E120-0XX /
R120-0XX
PA-98 / PH-XX
E120-0098 /
R120-0XX
- 17 24 Hour Emergency 1 (Alarm/Restoral) QA-XX / QH-XX
E101-0XX /
R101-0XX
UA-98 / QH-XX
E140-0098 /
R101-0XX
- 18 24 Hour Sprinkler 1 (Alarm/Restoral) SA-XX / SH-XX
E113-0XX /
R113-0XX
SA-XX / SH-XX
E113-0XX /
R113-0XX
- 19 24 Hour Water 1 (Alarm/Restoral) WA-XX / WH-XX
E154-0XX /
R154-0XX
WA-XX / WH-XX
E154-0XX /
R154-0XX
- 20 24 Hour Freeze 1 (Alarm/Restoral) ZA-XX / ZH-XX
E159-0XX /
R159-0XX
ZA-XX / ZH-XX
E159-0XX /
R159-0XX
- 21 24 Hour Latching Tamper 1 (Alarm/Restoral) UA-XX / UH-XX
E140-0XX /
R140-0XX
UA-98 / UH-XX
E140-0098 /
R140-0XX
- *22 Momentary Keyswitch Arm 1 (Alarm/Restoral) BA-XX / BH-XX
E130-0XX /
R130-0XX
BA-98 / BH-XX
E130-0098 /
R130-0XX
- *23 Maintained Keyswitch Arm 1 (Alarm/Restoral) BA-XX / BH-XX
E130-0XX /
R130-0XX
BA-98 / BH-XX
E130-0098 /
R130-0XX
- *24 LINKS Answer 1 (Alarm/Restoral) BA-XX / BH-XX
E130-0XX /
R130-0XX
BA-98 / BH-XX
E130-0098 /
R130-0XX
- 25 Interior Delay 1 (Alarm/Restoral) BA-XX / BH-XX
E130-0XX /
R130-0XX
BA 98 / BH-XX
E130-0098 /
R130-0XX
- *26 24 Hr Non Alarm 1 (Alarm/Restoral) BA-XX / BH-XX
E130-0XX /
R130-0XX
BA-98 / BH-XX
E130-0098 /
R130-0XX
- 27 Delayed 24Hr Waterflow 1 (Alarm/Restoral) SA-XX / SH-XX
E113-0XX /
R113-0XX
SA-XX / SH-XX
E113-0XX /
R113-0XX
- 28 Instant 24Hr Waterflow 1 (Alarm/Restoral) SA-XX / SH-XX
E113-0XX /
R113-0XX
SA-XX / SH-XX
E113-0XX /
R113-0XX
- 29 Auto Verified Fire 1 (Alarm/Restoral) FA-XX / FH-XX
E110-0XX /
R110-0XX
FA-98 / FH-XX
E110-098 /
R110-0XX
- 30 Fire Supervisory 1 (Alarm/Restoral) FS-XX / FV-XX
E200-0XX /
R200-0XX
FA-98 / FV-XX
E110-098 /
R200-0XX
- 31 Day Zone 1 (Alarm/Restoral) BA-XX / BH-XX
E130-0XX /
R130-0XX
BA-98 / BH-XX
E130-0098 /
R130-0XX